Installation
The VISTA-250FBP alarm system has been
designed to mount both quickly
and easily. It meets all applicable
requirements for UL commercial fire
and burglary installations.
Electrical
• Primary power: 18VAC @ 72VA ADEMCO
No. 1451
• Control Panel quiescent
current draw: 300mA
• Backup battery:
– 12VDC, 12AH min to 34.4AH max
– Lead acid battery (gel type)
• Alarm power: 12VDC, 1.7A max for
each notification (bell) circuit output
Total 2.3A @ 12V
• Aux. standby pwr: 12VDC, 1A max
• Total power: 2.3A at 12VDC, 3.4A at
24VDC from all sources
• Standby time: 24 hours with 1A standby
load using 34.4AH battery
Fusing: Battery input, aux. and
notification (bell) circuit outputs are
protected using PTC circuit protectors. All
outputs are power limited
• Optional 24-volt power supply, PS 24
supplies two 24 VFW, 1.7A full wave
rectified, unfiltered outputs
Main Dialer
• Line seize: Double Pole
• Ringer equiv.: 0.7B
• Formats: ADEMCO Low Speed,
ADEMCO 4+2 Express, ADEMCO High
Speed, ADEMCO Contact ID, Sescoa and
Radionics
• Dual phone line capability
(using 5140DLM module)
Cabinet Dimensions
• 18˝ H X 14.5˝ W X 4.3˝ D
Environmental
• Storage temp: 14° F to 158° F
(-10° C to 70° C)
• Operating temp: 32° F to 122° F
(0° C to 50° C)
• Humidity: 85% RH
• EMI: Meets or exceeds the
following requirements:
– FCC Part 15, Class B Device
– FCC Part 68
– IEC EMC Directive
Agency Listings Burglary
• UL609 Grade A Local Mercantile
Premises and Mercantile Safe
and Vault
• UL611/1610 Grades A, AA, Central
Station
• UL365 Grades A, AA Police Connect
Fire
• UL864/NFPA72 Local, Central Station
and Remote Station
• Factory Mutual
• California State Fire Marshal
• MEA
• UL985
SPECIFICATIONS
Notification
Appliance
5881
Wireless Receiver
(Max Two)
4204CF
Supervised
NAC
Module
4944SN
Addressable
Recessed Mount
Contact
Supports Up To 64
Conventional Two-Wire
Smoke Detectors
Supports Up To 64
Conventional Two-Wire
Smoke Detectors
4209U
Group Zoning
Module
4190SN
V-Plex Two-Zone
Expander
4193SN
Serial Interface
Module
4297
Isolation/
Extender Module
4190SN
5140MPS - 1*
5140MPS - 2*
Manual Pull Stations
Tamper Switch*
Flow Switch*
Low Temp Switch*
ECP-Bus
VGM (PTVGM)
VISTA
Gateway
Module
Symphony
V-Plex
Two-Zone
Expander
Panel Linking
Module
VISTA-250FBP VISTA-250FBP
PassPoint
5808W3
Photoelectric
Smoke/Heat
Detectors
5890
Wireless PIR
5808W3
Photoelectric
Smoke/Heat
Detectors
5800
Series
Wireless
Devices
5869
Commercial
Hold-Up Switch
5817CB
Wireless
Commercial
Transmitter
5816
Door/Window
Miniature
Transmitter
Q2260SN Multiplex
DUAL TEC
®
Motion Detector
Panel Linking
Module