ADEMCO 5110XM Setup Guide Page 22

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 21
5110XM Installation and Setup Guide
2-14
Battery Selection Table
Capacity Recommended Battery Comment
7AH Yuasa NP7-12
14AH Yuasa NP7-12 Connect two in parallel.
7. Connect the battery, referring to Figure 2-10.
The 5110XM runs a brief battery test once a minute to determine if battery leads are connected and runs an
extended battery test every 24 hours to determine if battery capacity is low (less than approximately 11.5VDC). If
a low battery condition exists the 5110XM's built-in Battery Trouble LED will light and a rapid beeping sound will
be heard from its built-in warning sounder. In addition, if a keypad is on the system, it will be displayed at the
control's keypad(s). These indications will stop when the low battery condition has been restored to normal (for
several minutes).
The 5110XM control comes with a dual battery harness, which allows up to two 12VDC lead acid batteries to be
connected in parallel to the control. Connect the battery(s) to the control using the dual battery harness as shown in the
figure below.
When connecting batteries in parallel:
Use batteries from the same manufacturer and with the same voltage and capacity rating.
Use batteries with approximately the same age and state of charge.
Use cables provided and observe polarity.
It is recommended that all batteries be replaced at the same time, even if only one battery has become weak.
U
L
The system provides monitoring of the system battery’s charger circuit. Program field 75 with the charger circuit
failure report code
BLACK
RED
BLACK
RED
12V
BATTERY
12V
BATTERY
(if required)
++
BLK
+ RED
BATTERY TABS
MAIN PCB
DUAL BATTERY HARNESS
(SUPPLIED)
NON-REPLACEABLE FUSE
(SEE NOTE 1)
BATTCONN
Figure 2-10: Connecting the Backup Batteries
NOTE: This fuse is intended to prevent the risk of battery harness flame-out when two batteries are used and one
battery is connected with proper polarity and the other battery is connected with reversed polarity. This fuse will not
open circuit under any other condition. Observe proper polarity when making connections!