1*42
CALL WAITING DEFEAT [0]
1=Yes; 0=No
.
1*43
PERM. KEYPAD BACKLIGHT [0]
1=enable; 0=disable When disabled, display lights when
any key is pressed, and turns off after period of keypad
inactivity.
1*44
WIRELESS KEYPAD [0]
TAMPER DETECT ENABLE
1=enable; 0=disable. Must
be "0" for Commercial Fire and UL installations.
1*45
EXIT DELAY SOUNDING [0]
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
1*47
CHIME ON BELL 1 [0]
1=enable; 0=disable
1*48
WIRELESS KEYPAD ASSIGNMENT [0]
0=disable; enter partition in which RF keypad used, 1-8.
Must be "0" for Commercial Fire and UL installations.
1*49
SUPPRESS TX SUPERVISION SOUND [1]
1=disable; 0=enable. Must be "0" for Commercial Fire and
UL installations.
1*52
SEND CANCEL IF ALARM + OFF [0]
1=no restriction; 0=within bell timeout period only
1*53
DOWNLOAD CALLBACK [0]
1=callback not required; 0=callback required; Must be "0" for
Commercial Fire and UL installations.
1*56
50/60 Hz CLOCK SPEED [0]
1=50 Hz; 0=60 Hz.
1*57
ENABLE 5800 RF BUTTON GLOBAL ARM [0]
1=enable; 0=disable
1*58
5800 RF BUTTON FORCE ARM [0]
Enter "1" to enable. If a zone is faulted after pressing button,
console will beep once. User should press button again
within 4 sec. to force bypass those zones. Enter "0" to
disable.
Must be "0" for Commercial Fire and UL installations.
1*60
ZONE 5 AUDIO ALARM VERIFICATION [0]
Enter 1 If 2-way audio (AAV) is being used; Enter 0 if it is
not.
Must be "0" for Commercial Fire and UL installations.
1*70
EVENT LOG TYPES
[1 0 0 0 1 0]
Alrm Chck Byps O/C Syst Test
1=enable; 0=disable
1*71
12/24 HOUR TIME STAMP FORMAT [0]
0=12 hour; 1=24 hour
1*72
EVENT LOG PRINTER ON-LINE [0]
0=disable; 1=enable
1*73
PRINTER BAUD RATE
1=300; 0=1200
[0]
Must be 1200 if using pager interface
1*74
RELAY TIMEOUT XX MINUTES [000]
| |
Enter the relay timeout,
0-127
in multiples of 2 minutes,
desired for #80 Menu Mode time driven event relay
command numbers "04/09" and #93 Menu Mode Relay
Programming output command "56".
1*75
RELAY TIMEOUT YY SECONDS [000]
| |
Enter the relay timeout,
0-127
seconds, desired for #80
Menu
Mode time driven event relay command numbers "05/10"
and #93 Menu Mode Relay Programming command "57".
1*76
ACCESS CONTROL RELAY FOR PART.[00]
|
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter 00-16; 00=none. Must be "00" for
Commercial Fire & UL..
1*77
LOG FIRST MAINTENANCE SIGNAL [0]
0=No Log; 1=Log first maintenance signal from each smoke
detector
3rd Page Programming Fields
(press *94)
2*00
NUMBER OF PARTITIONS [1]
Enter 1-8
2*01
DAYLIGHT SAVINGS TIME [04, 10]
| |
START/END MONTH Start End
00-12; if no daylight savings time, enter 00,00
2*02
DAYLIGHT SAVINGS TIME [1, 5]
|
START/END WEEKEND # Start | End
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last;
6=next to last; 7=3rd from last [1,5; 1st Sunday in April, last
in Oct.]
2*05
AUTO-ARM DELAY [15]
|
Enter the time between the end of the arming window and
the start of auto-arming warning period, in values of 1-14
times 4 minutes 00=instant; [15=no auto arm at all]. When
this delay expires, the Auto-Arm Warrning Period begins.
2*06
AUTO-ARM WARNING PERIOD [15]
|
This is the time during which the user is
warned to exit the
premises prior to the auto-arming of the system (beeps
every 15 seconds; "ALERT" displayed). Enter 01-15
minutes. 00=instant at end of arming delay .
2*07
AUTO-DISARM DELAY [15]
|
This is the time between the end of the disarming window
and the start of auto-disarming. Enter 01-14 times 4
minutes; 00=instant at end of window; 15=no auto-disarm.
2*08
ENABLE FORCE ARM FOR AUTO-ARM [0]
0=disable; 1=enable
2*09
OPEN/CLOSE REPORTS BY EXCEPTION [0]
1=enable; 0=disable; If enabled, only openings and closings
occurring outside the scheduled opening/closing windows
will trigger dialer reports. Opening reports will also be
suppressed during the closing window, in order to prevent
false reports when the user arms the system and then
reenters the premises to retrieve a forgotten item.
2*10
ALLOW DISARMING ONLY DURING [0]
ARMING/DISARMING WINDOWS
0=disable; 1=enable
See system-wide field 2*11 if enabling field 2*10. This
feature adds high security to the installation.