ADEMCO Vista-128FB User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 68
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
11
2*11
ALLOW DISARM OUTSIDE WINDOW [0]
IF ALARM OCCURS
Used only if field 2*10 (partition-specific field) is set to "1". If
this field is enabled ("1") the system can be disarmed
outside the disarm window if an alarm has occurred. If "0",
disarming can only be done during the disarm window. If
field 2*10 is set to "0" for a partition, this field has no effect
for that partition.
2*18
ENABLE GOTO FOR THIS PARTITION [0]
1=Allow log-on from other partitions; 0=disable
2*19
USE PARTITION DESCRIPTORS [0]
0=disable; 1=enable
2*20
ENABLE J2 TRIGGERS by PARTITION [1]
0=disable for displayed partition; 1=enable for displayed
partition
2*21
ENABLE SUPERVISION PULSES FOR LRR
TRIGGER OUTPUTS [00000]
| | |
FB PST
Used for supervised connection to 7920SE.
Enter 0 to disable or 1 to enable the listed outputs.
F= Fire; B= Burglary; S= Silent panic/duress. Enter 1 for
Commercial Burglary and UL.
2*22
DISPLAY FIRE ALARMS OF [0]
OTHER PARTITIONS
0=No; 1=Yes.
2*23
DISPLAY BURG & PANIC ALARMS OF [0]
OTHER PARTITIONS
0=No; 1=Yes.
2*24
DISPLAY TROUBLES OF OTHER [0]
PARTITIONS
0=No; 1=Yes.
4th Page Programming Fields
(press *94)
3*00
DISPLAY TRBL INSTEAD OF CHECK [0]
3*01
FIRE DISPLAY LOCK [0]
0=scroll all alarms; 1=lock display of first fire alarm.
3*12
ZN TYPE 18 DELAY USE [1]
0=Check Displayed; 1=Trbl Displayed
3*13
SUPV. N.O./N.C. SELECTION [0]
0=Supv. on short/trouble on open; 1=supv. on short or open
3*14
WATERFLOW SILENCE OPTION [0]
0=Silence on Code + OFF; 1=Silence when waterflow
restores
3*15
ALARM BELL SOUND [1,0]
0=pulsed; 1=steady
Bell 1Bell 2
3*16
DELAY for ZONE TYPES 17 & 18 [00]
|
(Waterflow & FIre Supv) Enter 00-15 times 2 seconds
3*17
ALTERNATE FUNCTION (TAMPER) [0]
FOR ZONE 6
0=disabled; 1=enabled
3*18
EXTENDED DELAY FOR TYPES 17&18 [0]
0=No; 1=Yes
3*19
ENABLE J2 HEADER PRINTER PORT [0]
0=pins 5&9 function as per field 3*20; 1=pins 5&9 act as
printer RXD & DTR
3*20
TRIGGER OUTPUTS SELECTION [0]
0= LORRA full connection & Remote Console Sounder;
1=LORRA limited conn. & Keyswitch LEDs; 2=LORRA fire
only conn. & 5140LED
3*21
MAX # OF DIALER ATTEMPTS [8]
1-8 (3, 4 or 5 for NFPA72 compliant systems when a
secondary phone number is programmed (field *34)
3*30
DIALER SELECTION [1,0]
1=enabled; 0=disabled
Main Backup
3*31
BACKUP DIALER TOUCHTONE/ROTARY
[0]
1=TouchTone; 0=Rotary
3*50
ZONE TYPE RESTORE ENABLES
FOR ZONE TYPES 16-18
16 17 18
1 = enabled; [0 = disabled]
3*55
RESET ON SECOND OFF FOR BELL 1
[0]
1 = enabled; 0 = disabled
3*56
RESET ON SECOND OFF FOR BELL 2
[0]
1 = enabled; 0 = disabled
3*57
BELL 2 & AUX. RELAY CONFIRM
ARM DING
Bell 2 AUX.
1=enable; [0=disable] . Must be 1 for UL Commercial
Burglary.
3*59
ENABLE BELL 2 & AUX. RELAY
CHIME ANNUNCIATION
Bell 2 AUX
1=enable; [0=disable]
3*60
BELL 2 & AUX. RELAY TIMEOUT
| |
00-15 times 2 minutes; 00=no timeout [00,00]
Bell 2 AUX
Must be minimum of 16 minutes for UL Burglary
installations.
3*61
AUX. RELAY FUNCTION [1]
0=Trouble/supervisory; 1=Alarm, silenced by code + OFF
2=Smoke Detector Reset; 3=Battery Save; 4=Alarm,
silenced by code + [#] + 67
3*82
ENABLE BURG. FEATURES ON PART. 1 [1]
1=enable; 0=disable; “0” disables AWAY, STAY, MAX,
TEST, INSTANT & CHIME functions
3*85
ENABLE FIRE & SYSTEM ZONE BYPASS [1]
0=not enabled; 1=only installer can bypass]; 2=only installer & master
user can bypass. Applies to fire zone types 9, 16, 17 & 18 and system
zones 70-77. Applies to Partition 1 only.