Section 16. OUTPUT DEVICE PROGRAMMING (*80
Menu Mode)
Programming Options Defined
The following will help you understand the programming of Output Devices when
using
*
80 and
*
81 modes. The options used to start and stop these devices are
described below, followed by the actual screen prompts and available entries.
IMPORTANT: Relays and
output devices are not
recommended for life safety
applications.
The letter(s) in parentheses after each function described below, such as (A)
after ACTION, are those that appear in the various summary displays of
programmed data during programming.
ACTION (A) The "ACTION" of the device is how the device will respond
when it is activated by the "START" programming. There are
four different choices of actions:
ACTIVATE for 2 SECONDS and then reset.
ACTIVATE and REMAIN ACTIVATED until stopped by
some other event.
PULSE ON and OFF until stopped by some other event.
NOT USED when the device is not used.
START
(STT)
The "START" programming determines when and under what
conditions the device will be activated. The following START
options are available
:
Start By Event
1. Event (EV) is the condition (Alarm, Fault, Trouble) that must
occur to a zone or group of zones (zone list) in order to
activate the device. These conditions apply only when a zone
list is used. The different choices for "EVENT" are listed below
and in the “Programming Output Relays & Powerline Carrier
devices” section that follows.
• ALARM Relay activates upon any alarm in an assigned
zone in the zone list.
• FAULT Relay activates upon any opening or short in
an assigned zone in the zone list.
TROUBLE Relay activates upon any trouble condition in
an assigned zone in the zone list.
• NOT USED Relay action is not dependent upon one of the
above events.
2. Zone List (ZL) is a group of zones to which the “EVENT”
applies in order to activate a particular device. Note that
there are a total of 3 output device related zone lists that can
be programmed in
*
81 menu mode; when the selected
EVENT (Alarm, Fault or Trouble) occurs in any zone in the
selected “Start” ZONE LIST (1, 2, or 3), activation of the
selected device will START.
Start by Zone Type or System Operation
1. If a System Operation, such as “DISARMING” or “ANY FIRE
ALARM,” is to activate the device, the appropriate choice
would also be entered under the “ZONE TYPE” option.
“ZONE TYPE” is used independently of the “EVENT/ZONE
LIST” combination.
If a "ZONE TYPE" is chosen, any zone of that response type
going into alarm, trouble, or fault will cause the device to
activate as selected in "ACTION.” If the same “ZONE TYPE” is
also chosen for the STOP programming, any zone of that type
that restores will de-activate the device.