– 11 –
1*29 RF TX LOW BATTERY REPORTING [0]
1=enable; 0=disable
Must be 1 for UL installations.
1*30 RF RCVR CHECK-IN INTERVAL [02] |
02-15 times 2 hours; 00 disables supervision
Maximum is 2 (4 hr) for UL installations.
1*31 RF XMITTER CHECK-IN INTERVAL [02] |
02-15 times 2 hours; 00 disables transmitter supervision
Maximum is 2 (4 hr) for UL installations.
1*33 TOUCHTONE W/ROTARY BACKUP [0]
1=enable; 0=disable
1*34 COMM. SPLIT REPORTING [0]
0=no; 1=alarms and alarm restores primary, others
secondary; 2=open/close, test secondary, others primary;
3=fire alarms and fire restores to primary and secondary, all
others to secondary. See 51 for comments if using with
dual reporting.
NOTE: Split reporting should not be used with Dynamic
Signaling.
1*35
ACCESS CONTROL DIALER ENABLES - Not Used.
[0 0 0 0 0 0]
Trace
Trbl
Byp
Not Used
Syst
Alm
1=enable; 0=disable
Must Be Set To “0”.
1*42 CALL WAITING DEFEAT [0]
1=enable; 0=disable
1*43 PERM. KEYPAD BACKLIGHT [0]
1=enable; 0=disable, when disabled, display lights when any
key is pressed, and turns off after period of keypad inactivity.
1*44 WIRELESS KEYPAD TAMPER DETECTION Not
Used. Must be set to “0”.
[0]
1=enable; 0=disable.
1*45 EXIT DELAY SOUNDING [1]
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
NOTES:
Must be set to “0” in partition 1 for fire systems.
Must be enabled “1” for SIA installations.
See page 32, “SOUND OPTION”, prompt for disabling the
entry/exit beeps on individual keypads.
1*47 CHIME ON BELL 1 [0]
1=enable; 0=disable
1*48 WIRELESS KEYPAD ASSIGNMENT - Not Used. Must
be set to “0”.
[0]
0=disable; enter partition in which RF keypad used, 1-8.
1*49 SUPPRESS TX SUPERVISION SOUND [1]
1=disable; 0=enable.
Must be "0" for Commercial Burglary and Fire installs.
1*52 SEND CANCEL IF CODE + OFF [1]
1=no restriction; 0=within bell timeout period only.
Must be enabled “1” for SIA installations.
1*53 DOWNLOAD CALLBACK [0]
1=callback not required; 0=callback required.
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*55 EUROPEAN DATE FORMAT [0]
0=disable (mm/dd/yy); 1=enable (dd/mm/yy).
1*56 AC 50/60 Hz CLOCK SPEED [0]
1=50 Hz; 0=60 Hz.
1*57 5800 RF BUTTON GLOBAL ARM [0]
1=enable; 0=disable
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*58 5800 RF BUTTON FORCE ARM [0]
1=enable. If a zone is faulted after pressing button, console
will beep once. User should press button again within 4 sec.
to force bypass those zones. 0=disable.
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*60 ZONE 5 AUDIO ALARM VERIFICATION [0]
Enter 1 if 2-way audio (AAV) is being used; Enter 0 if it is not.
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*69 PRINTER TYPE - Not used. Must be set to “0”.
[0]
Enter 0 if you are using a parallel printer connected to the
VA8201 Alpha Pager Module.
Enter 1 if you are using a serial printer.
1*70 EVENT LOG TYPES
[1 0 0 0 1 0]
Alarm
Chk
Byp
O/C
Syst
Test
1=enable; 0=disable
1*71 12/24 HOUR TIME STAMP FORMAT [0]
0=12 hour; 1=24 hour
1*72 EVENT LOG PRINTER ON-LINE - Not Used. Must Be
Set To “0”.
[0]
0=disable; 1=enable
1*73 PRINTER BAUD RATE - Not Used. Must Be Set To
“0”..
[0]
1=300; 0=1200
1*74 RELAY TIMEOUT XXX MINUTES [000] | |
Enter relay timeout, 0-127 in multiples of 2 minutes, desired
for #80 Menu Mode time-driven event relay command
numbers "04/09" and #93 Menu Mode Output Programming
output command "56."
1*75 RELAY TIMEOUT YYY SECONDS [000] | |
Enter relay timeout, 0-127 seconds, desired for #80 Menu
Mode time driven event relay command numbers "05/10" and
#93 Menu Mode Output Programming command "57."