10Sprinkler System Control Valve Supervision: The main reason for sprinkler system failure is do toinadvertent control valve closure. A closed control

Page 3 - MyWebTech

11ADEMCO Panel ComparisonPANELMAXzonesHW-StdHW-ExpV-Plex5800zonesKeyfobzonesPartitionsZoneDoublingKeyswitchUsers OutputsEventLogLine FaultVISTA-20PS48

Page 4

12ADEMCO Panel ComparisonPANEL2 wiresmokes4 wiresmokeAccessControlSingleButtonArmingSchedulesProgramablezone typesKeypadmacrosPager42854286AAVVISTA-20

Page 5

13ADEMCO Panel ComparisonPANELAuxPowerAlarmPowerMax#KeypadsECPRadioMax#4204Max#4219/4229Vent ZoneCustomWordsUp &AboutX-10TransformerVISTA-20PS12v6

Page 6

14ADEMCO Panel ComparisonPANELSwingerShutdownAutoStayCrossZoningExitAlarmQuickExit/ExitRestaurantExit DelayResetPanelLinkingNightStayModeChime byZoneD

Page 7

15The VISTA-20PS is an eight-zone control panel specifically designedto support Honeywell’s intuitive graphical user interfaces. The graphicuser inter

Page 8

16SPECIFICATIONS:Electrical• Aux. power 12VDC, 600mA maximum• Seven hour standby at 400mA aux. load with four amp hourbattery• 16.5VAC/25VA transforme

Page 9

17• Provides nine style-B hardwired zones• Supports up to 119 additional zones using a built-in polling(multiplex) loop interface• Supports up to 128

Page 10 - Glossary of Terms

18Additional Features:Basic Hardwired ZonesProvides nine style-B hardwired zones with the following characteristics:• EOLR supervision (optional for z

Page 11 - ADEMCO Panel Comparison

19New Enhancement Panel LinkingPanel Linking allows multiple control panels to be networkedtogether and controlled from any keypad in the system:• Con

Page 12

2Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 13

SPECIFICATIONS:ORDERING:Part No. DescriptionVISTA-128BP Partitioned Commercial Burglary Alarm PlatformCompatible DevicesSee compatibility chart for co

Page 14

21ADEMCO VISTA-250BP 250 Zone UL Commercial Burglary Control Panel • Provides nine style-B hardwired zones• Supports up to 241 additional zones using

Page 15 - ADEMCO VISTA-20PS

22NotificationAppliancesAdditional FeaturesBasic Hardwired ZonesProvides nine style-B hardwired zones with the following characteristics:• EOLR superv

Page 16

23New Enhancement PANEL LINKINGPanel Linking allows multiple control panels to be networkedtogether and controlled from any keypad in the system:• Con

Page 17 - ADEMCO VISTA-128BP

24SPECIFICATIONS:ORDERING:Part No. DescriptionVISTA-250BP Partitioned Commercial Burglary Alarm PlatformCompatible DevicesSee compatibility chart for

Page 18

25• Supports addressable V-Plex access control points usingVistaKey (1 to 4 doors)• Supports up to 16 doors of access control using Vista Gateway Modu

Page 19

26ADEMCO VISTA-32FB Commercial Fire/Burg/CCTV and Access Control Platform Additional Features• Notification Appliance Circuits (two):– Programmable– T

Page 20

27ADEMCO VISTA-32FB Commercial Fire/Burg/CCTV and Access Control Platform ApplicationsThe VISTA-32FB control is well suited for a variety ofapplicatio

Page 21 - ADEMCO VISTA-250BP

28ADEMCO VISTA-32FB Commercial Fire/Burg/CCTV and Access Control Platform SPECIFICATIONS:ORDERING:Compatible DevicesSee compatibility chart for comple

Page 22

29• Eight hardwired zones standard, expandableto 120 V-Plex addressable points/zones or 128 wireless points/zones• Can control eight separate areas in

Page 23

3ProfileWe are a world leader in comfort and security, offering state-of-the-art solutions for residential and commercial installations.Millions of bu

Page 24

Additional Features• Notification Appliance Circuits (two):– Programmable– Temporal code compliant– Individually silenceable• Programmable on-board au

Page 25 - ADEMCO VISTA-32FB

NotificationAppliance5881Wireless Receiver(Max Two)6139R32 CharacterRed-AlphaKeypad4204CFSupervisedNACModule4293SNV-Plex Adapter4944SNAddressableReces

Page 26

32SPECIFICATIONS:ORDERING:Compatible DevicesSee compatibility chart for complete listAuxiliary Devices• 6160CR – Red Alpha Keypad• 6139R – Red Alpha K

Page 27

33FEATURES:Designed to integrate seamlessly with CCTV, accesscontrol and Honeywell’s full range of fire and burglarycomponents, the ADEMCO VISTA-250FB

Page 28

34ADEMCO VISTA-250FBP/VISTA250FBP-24250 Zone UL Commercial Fire/Burglary Control Panel 5192 Series Smoke Detectors4208UEight-ZoneExpansionModule4193SN

Page 29 - FEATURES:

35ADEMCO VISTA-250FBP/VISTA250FBP-24250 Zone UL Commercial Fire/Burglary Control Panel NotificationAppliance5881Wireless Receiver(Max Two)6139R32 Char

Page 30 - V-PLEX Loop

36SPECIFICATIONS:ORDERING:Compatible DevicesSee compatibility chart for complete listAuxiliary Devices• 4204 – Relay Module, four form C contacts• 420

Page 31

373737The 5110XM is a UL Listed, microprocessor based fire alarmcontrol/communicator that supports five hardwired zones. It may beused as a slave Digi

Page 32 - SPECIFICATIONS:

383838InstallationThe 5110XM Fire Alarm Communicator (DACT) has beendesigned to mount both quickly and easily. It meets allapplicable requirements for

Page 33

39Honeywell’s 6150 Deluxe Keypad is easy to installand simple to use. The attractive white consoleblends perfectly with any décor, and features aconto

Page 34 - V-Plex Loop

4AAV: Audio Alarm Verification, also known as 2-way voice to the central station. The LYNX-REN has this feature built-in. TheLYNX-R can use the LYNX-A

Page 35

406150VTalking Fixed English Display Keypad The 6150V Talking Fixed English Display Keypad is easyto install and simple to use. It takes the guesswork

Page 36

4141416150RFDeluxe Fixed English Integrated Keypad/ReceiverFEATURES:41• 6150 Deluxe Keypad• 5881ENM 16-Zone Wireless Receiver• 5800TM Status Transmitt

Page 37 - APPLICATIONS:

Honeywell’s 6160CR is an addressable remote keypadintended for use in commercial fire applications withADEMCO control platforms. The keys are continuo

Page 38

43Symphony & Symphony-iGraphic Touchscreen DisplaysSecurity• Arm System– AWAY– STAY– NIGHT• Exit/Entry delay countdown• User codes: Allows authori

Page 39

44Symphony & Symphony-iGraphic Touchscreen DisplaysEvent LogLighting and Appliance ControlLighting and Appliance ControlCustomized display for con

Page 40

45Symphony & Symphony-iGraphic Touchscreen DisplaysSPECIFICATIONS:• Symphony with power supply – Part number 8132PK• Symphony-i with power supply–

Page 41

46• 8 or 24 LED annunciators with sounder• Power and trouble LEDs• Silence and reset switch• Lamp test switch• Fully supervised • Operates on Commerci

Page 42

LOCAL TEST MODE:Prior to installation the local test mode should be performed.With only power applied to the FSA module, press any buttonwithin 3 seco

Page 43 - Symphony & Symphony-i

48VistaView-100 CCTV SwitcherHoneywell’s VistaView-100 module is a CCTV switcher thataccepts four video inputs, switching them to two video outputs.Th

Page 44

49VistaView-100 CCTV SwitcherGeneral Information:The ADEMCO VistaView-100 module is a CCTV switcher thataccepts 4 video inputs, switching them to 2 vi

Page 45

5Automatic Fire Detectors: Fire produces well-defined signatures such as thermal energy (heat), smoke, and radiantenergy. Fire alarm system designers

Page 46 - FSA-8/FSA-24

50Dealer Benefits• Helps reduce installation material and labor costs by eliminatingthe need to install additional control panels, software and wiring

Page 47

51VistaKey-SK Access ControlPERIPHERAL DEVICES:ORDERING:The following listing identifies some peripheral devices that can be used with VistaKey-SK.De

Page 48 - VistaView-100

52VISTA Gateway Module (VGM) Access Control Interface• 8 bit microprocessor.• EEPROM based configuration storage.• Echelon Network interface implemen

Page 49

53VISTA Gateway Module (VGM) Access Control InterfaceAPPLICATIONS:Once the appropriate configuration information has beentransferred from the PassPoi

Page 50 - VistaKey-SK

54FEATURES:Honeywell’s 4208SN Remote Point Module (RPM) is an eight-zoneexpander that allows the use of available expansion zones on ADEMCOcontrols th

Page 51

55FEATURES:Honeywell’s 4208U Remote Point Module (RPM) is an eight-zone expanderthat allows the use of available expansion zones on ADEMCO controls th

Page 52 - VISTA Gateway Module (VGM)

56FEATURES:• Can be used on controls that support up to 250 zones• Provides up to six Class B supervised zones using external10k EOL resistors and two

Page 53

57ORDERING:Part No. Description4208SNF Universal Class/B Expander ModulePhysical• 6-7/16" W X 4 1/4 H X 1-1/4" D(163mm X 108mm X 32mm)Electr

Page 54 - 4208SN

585817CB Commercial Wireless Transmitter• Use with commercial and household fire/burglaryinitiating devices, including sensors, contact switches and p

Page 55

595800 Series Remote Controls give your customers one-touch control of their securitysystems lights, and appliances.5800 SERIES Remote Controls5804Fo

Page 56 - 4208SNF

6Expansion: The type of hard wired and RF (wireless) zone expansion. VISTA-20P, VISTA-20PS use 4219 or 4229modules for zone expansion. The VISTA-128BP

Page 57

605890PIPIR MotionDetector with Pet Immunity5890PIR MotionDetector5819ShockProcessor andTransmitter5819WHSShockProcessor andTransmitter5852FlexGuard®A

Page 58 - 5800 SERIES

61V-Plex Devices 4101SNAddressable Relay Module4208SNFUniversal Class A & Class B Expander Module4293SNAdapter5192SDTPhotoelectric Smoke Detector

Page 59

62FEATURES:• Reports alarm and other signals easily over the Internet• Allows remote control of the protected premise withoptional AlarmNet service• E

Page 60

63SPECIFICATIONS:ORDERING:Part No. Description7845i Internet CommunicatorEnclosure Dimensions: • 6.5" H x 7.5" W x 1.5" DEnvironmental

Page 61 - V-Plex Devices

64FEATURES:• Capable of receiving Internet messages from AlarmNet,including the entire base of AlarmNet radios and Internettransmitters• 7810iR can be

Page 62

657810iR Internet ReceiverSPECIFICATIONS:ORDERING:Part No. Description7810iR Internet ReceiverEnclosure Dimensions: • 5 3/4”H x 8”W x 1 1/4” DEnviron

Page 63

66Honeywell’s AlarmNet 7720ULF is a self-contained fire controland long-range radio transmitter that is UL listed for propertyprotection and life safe

Page 64 - 7810iR

677720ULF UL Listed Radio TransmitterSPECIFICATIONS:ORDERING:Installation:The 7720ULF should be mounted indoors, in an area that iseasily accessible.

Page 65

68ApplicationsProvides the highest level of security available. Dealers can connect the 7830R to almost any security system to transmit alarmsand supe

Page 66 - 7720ULF

697830RAlarmNet-M TransceiverSPECIFICATIONS:ORDERING:The 7830R is wired to the panel per wiring diagram providedwith the radio. Observe the LED once t

Page 67

7H/W zones built-in: The number of standard hard wired zones included with the panelInitiating Device: A system component that originates transmission

Page 68

70ApplicationsProvides the highest level of security available. Dealers can connect the 7845CZ to almost any security system to transmit alarms and su

Page 69

717845CZCellular TransceiverORDERING:Part No. Description7845CZ Subscriber TransceiverInstallation:After the radio is powered up, the LED should be ob

Page 70

72Honeywell’s 7845CV2 Control Channel Cellular SubscriberTransceiver takes advantage of the latest advances in ControlChannel Cellular design—offering

Page 71

737845CV2Control Channel Cellular Subscriber TransceiverElectricalPower:– Powered from panel @ 100mA max.,if current limit mode used– Optional 12.5VDC

Page 72 - Replaces

747845CFCellular Fire Radio Control Channel Subscriber TransceiverDesigned as a cellular backup for fire applications, Honeywell’s7845CF takes advanta

Page 73

757845CFCellular Fire Radio Control Channel Subscriber TransceiverElectrical• Voltage Input: 9.6–13.8VDC, 12VDC nominal• DC current drain: 400mA (max

Page 74

767845CZFCellular Fire Radio Control Channel Subscriber TransceiverDesigned as a cellular backup for fire applications,Honeywell’s 7845CZF works with

Page 75

777845CZFCellular Fire Radio Control Channel Subscriber TransceiverElectrical• Voltage Input: 9.6–13.8VDC, 12VDC nominal• DC current drain: 400mA (ma

Page 78

8Partitions: Some control panels have the ability to be programmed for multiple partitions, which allows the single controlto protect different areas

Page 79

801-800-645-7492www.honeywell.com/securityL/COMPNLGD/D 5/04

Page 80 - 1-800-645-749

9Signaling Line Circuit (SLC): A circuit to which initiating and/or notification appliances are connected. The signalreceived does identify the indivi