– 18 –
PROMPT
EXPLANATION
Each zone must be assigned a zone type, which defines the way in which the system responds to faults in
that zone. Refer to the
Zone Type Definitions
section in the
VISTA-128FBP/VISTA-250FBP
Installation and
Setup Guide
for detailed definitions of each zone type. Enter the zone type desired (or change it, if
necessary). Available zone types are listed below.
00 = Assign for Unused Zones 14 = CO Detector Alarm
01 = Entry/Exit #1, Burglary 16 = Fire With Verification
02 = Entry/Exit #2, Burglary 17 = Waterflow
03 = Perimeter, Burglary 18 = Fire Supervisory
04 = Interior Follower, Burglary 19 = 24-Hour Trouble
05 = Trouble Day/Alarm Night 20 = Arm–STAY†
06 = 24 Hr. Silent Alarm 21 = Arm AWAY†
07 = 24 Hr. Audible Alarm 22 = Disarm†
08 = 24 Hr. Auxiliary 23 = No Alarm Response (e.g., relay activation)
09 = Fire Without Verification 27 = Access Point – Not Used
10 = Interior Delay, Burglary 28 = MLB Supervision (if VGM installed) – Not Used
12 = Panel Link Supervision – Not
Used
29 = Momentary Exit (used with VistaKey module) - Not Used
13 = Remote P/S
010 ZONE TYPE
PERIMETER 03
Zone number 010 and
Zone Type 03 entry shown
These are special zone
types used with 5800
Series Wireless
Pushbutton Units that
result in arming the system
in the STAY or AWAY
mode, or disarming the
system, depending on the
selection made.
Press [] to continue.
010 Arm w/ Fault?
1 = YES 0 = NO 0
If you selected response type 1, 2, 4, or 10, this prompt appears. Enter 1 to enable arming of the partition
with this zone faulted. The zone must be restored (see Force Arming, the next prompt) before the exit delay
expires otherwise the system starts the entry delay and must be disarmed, or an alarm occurs.
010 Force Arming?
1 = YES 0 = NO 0
If you entered 1 (YES) at the previous prompt, this prompt appears. Enter 1 to enable the system to
automatically bypass the zone if it is faulted at the end of the exit delay.
If you enter 0 to disable and the zone is faulted at the end of exit delay, the system either performs the exit
error logic, if field 120 is enabled, or an alarm occurs.
NOTE: Force Arming cannot be enabled for UL installations.
010 Vent zone ?
1 = YES 0 = NO 0
If you selected response type 3, this prompt appears. Enter 1 to enable the arming of the partition with this
zone faulted (force arm). The zone is automatically bypassed.
NOTE: The zone may be unbypassed simply by restoring the zone (e. g., closing the window), if the Vent
Re-arm option (next prompt) for the zone is enabled.
Enter 0 to disable.
Press [] to continue.
010 Vent Re-arm ?
1 = YES 0 = NO 1
If you entered 1 (YES) at the previous prompt, this prompt will appear. Enter 1 to enable the system to
automatically unbypass the zone when it is restored (e.g., by closing the window).
Enter 0 to disable. The zone is bypassed for the duration of the armed period regardless of the zone status.
Press [] to continue.
010 STAY MODE
None 0
If you selected response type 1, 2, 3, 4, 5, or 10, this prompt will appear. Enter the STAY mode for this
zone (0-2).
0 = None. The zone is not bypassed when the partition is armed STAY.
1 = Stay 1. The zone is automatically bypassed when the user enters [User Code] + [3] (STAY) + [1].
2 = Stay 2. The zone is automatically bypassed when the user enters [User Code] + [3] (STAY) + [2].
NOTES:
0 (None) cannot be selected for response types 4 and 10.
Response types 4 and 10 are defaulted for STAY mode 1.
If the user enters [User Code] + [3] (STAY) + [3], all zones assigned to Stay mode 1 and 2 in the partition
are automatically bypassed.
If none of the zones in the partition are assigned to Stay mode 2, then when the user enters [User Code] +
[3] (STAY), all zones assigned to Stay mode 1 are automatically bypassed.
Press [] to continue.
010 Auto-stay ?
1 = YES 0 = NO 0
If you selected response type 1, 2, 3, 4, 5, or 10, this prompt will appear. Enter 1 to enable. The zone is
automatically bypassed if none of the entry/exit zones are opened during the exit delay time (no one exits the
premises). Enter 0 to disable.
NOTES: All zones enabled for auto-stay except types 3 and 5 have exit delay time when the partition is
armed. If auto-stay is enabled, make sure at least one zone is programmed for entry/exit in the same
partition, otherwise this zone will be automatically bypassed every time the partition is armed.
Press [] to continue.