Menu Mode Programming
5-17
PROMPT
VALID ENTRIES EXPLANATION
C
01 Enter Zn No.
12
Zone Number
If zone number was selected, this screen appears.
Enter the desired zone number associated with
this output number.
Press [
] to continue.
Enter the zone event that will activate this output.
01 Enter Event 0 = restore; 1 = alarm
Restore 0 2 = fault; 3 = trouble
Press [
] to continue to the “Output Action”
prompt
01 Output Action
Close for 2 sec 1
Output Action
0-6 = see list at right
Enter the desired device action as listed below.
Press the [
] key to continue.
0 = off 4 = Change
Device State
1 = Close for 2 seconds 5 = Duration 1
(see data field
*177)
2 = Close and Stay Closed 6 = Duration 2
(see data field
*177)
3 = Continuous Pulse on & off (1 sec ON, 1 sec
OFF)
Enter Output No.
R02 02
Output Number
01-04 = output no.
17-18 = on-board triggers
Enter the device output number (programmed in
*79 Menu Mode) you want associated with this
output.
Press [
]
to continue.
02 A E P TRIG
R02 1 1 3 ZL=1
Summary Screen
A summary screen appears showing the
programmed settings.
Press [
] to continue.
About Zone Lists (
81 Menu Mode)
Zone lists let you group individual zones for use with certain system actions. The following table shows
the available zone lists and their purposes:
List No.
Used for…
1,2 general purpose
3 chime-by-zone
4 linked zones
5 night-stay zones
6,7 general purpose
8 final contact set zones or general purpose
9 zones that activate pager 1 or general purpose
10 zones that activate pager 2 or general purpose
11 general purpose
12 exit zones (enabled in field *88)