VISTA-128BP/VISTA-250BP Installation and Setup Guide
3-26
Step Action
4 Connect the leads to TB1 in the following
order:
a. All ground leads to terminals 2, 5, and 9.
b. The DSM, (optional) RTE, and General
Purpose leads to terminals 6, 7, and 8,
respectively.
c. Door strike (or mag lock) lead to terminal
10.
d. Local +12V or +24V supply lead to
terminal 1.
e. Local +12V or +24V supply lead to the N/C
relay terminal 11 (if a mag lock is being
used), OR to the N/O relay terminal 10 (if
a door strike is being used).
5 Connect the (–) polling loop and (+) polling
loop leads (from the VISTA-128BP/VISTA-
250BP) to terminals 4 and 3, respectively.
6 Set the Address Select switch to the desired
access door number (1-15).
7 Repeat steps 1 through 6 for each VistaKey
being installed.
Connecting the Card Reader
Lead from Reader Lead Color To VistaKey TB3
Terminal #
Green LED Orange 1
Ground* Black 2
DATA 1 (Clock) White 3
DATA 0 (Data) Green 4
+5VDC Red 6
+12VDC Red 7
* TB-3 Terminal 5 is also a ground and may be used
instead of terminal 2. Terminals 2 and 5 are a common
ground.
Connect to +5VDC OR +12VDC per reader
manufacturers specification.
+
WEEKLY TESTING IS REQUIRED
TO ENSURE PROPER OPERATION
OF THIS SYSTEM.
POLE Door Strike/Mag Coil
DATA 1 (WHITE)
DATA 0 (GREEN)
NOTE 1: USE UL LISTED ENERGY CABLE FOR ALL CONNECTIONS.
NOTE 2: VISTAKEY TB3 TERMINAL 5 IS A GROUND AND MAY BE
USED INSTEAD OF TB3 TERMINAL 2. TB3 TERMINALS 2 AND 5 ARE
A COMMON GROUND.
NOTE 3: WHEN USING TRIGGER TO TURN ON AN LED OR BUZZER,
RETURN HIGH SIDE OF LED OR BUZZER TO TB3 TERMINAL 7.
TRIGGER RATING IS 15mA AT 12VDC.
+5V
GND
TRIGGER (SEE NOTE 3)
+12V (RED)
ZONE C (General)
ZONE A (DSM)
ZONE B (RTE)
POLLING LOOP -
14V MAX (12V @ 85-160mA Nominal)
POLLING LOOP +
GND
GND
GND
N/O DOOR STRIKE POWER
N/C MAG COIL POWER
2
3
4
5
6
7
8
11 1223456789101
RELAY CONTACT RATINGS:
3A @ 28VDC MAX. (RESISTIVE LOAD)
TB 1
TB 3
1
READER INTERFACE CABLE
GND (BLACK)
RDR LED (ORANGE)
TO ALARM SYSTEM
CONTROL PANEL
POLLING LOOP TERMINALS.
NO
CONNECTION
VISTAKEY
THIS DEVICE COMPLIES WITH PART 15 CLASS A
LIMITS OF FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS:
(1) IT MAY NOT CAUSE HARMFUL INTERFERENCE.
(2) IT MUST ACCEPT ANY INTERFERENCE THAT
MAY CAUSE UNDESIRED OPERATION.
K1
DOOR
CONTROL
RELAY
FOR ADDITIONAL RATINGS AND
SPECIFICATIONS, REFER TO
INSTALLATION INSTRUCTION
FOR THE VISTAKEY-SK.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARDS 70 &
74 (NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA. 02269).
PRINTED INFORMATION DESCRIBING PROPER
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
TO TB1, 11 OR 12
+ 12 VDC TO ONLY
ONE OF THESE INPUTS.
(FROM TB1-1)
Figure 3-31: Wiring the VistaKey
Access Control Using the PassPoint Access Control System
The VISTA-128BP/VISTA-250BP interfaces with the
PassPoint ACS via the VISTA Gateway Module
(VGM). The VGM is connected between the ECP bus
(keypad terminals) of the control and the network bus
of the PassPoint ACS.
The control sends the VGM its status information,
event log entries, and entry/exit requests (inputs
programmed with response type Access Point) from
keypads, hardwired zones, and RF transmitters.