ADEMCO Vista-128FB Setup Guide Page 71

  • Download
  • Add to my manuals
  • Print
  • Page
    / 147
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 70
Section 4 – Programming
4-9
230 Enter 1 to enable the Alpha Pager Module.
231 - 288 Paging service parameters. The
events (e.g., field 2*39) must be programmed
for the pager to work.
Fields for programming the delay times (e.g.
2*36 and 2*37 for pager 1) are relevant only
when using numeric format for the pager.
NOTE: For Event Log Report Codes program
System Group #2 in the #93 Menu Mode.
Programming for 4100SM
05 Enter 1 to print all zone faults/restores; enter
0 to print only events enabled in field 170
14 Enter 1 if using Home Automation (cannot
use both serial printer and Home Automation)
169 Not applicable
170 Event Log Types (1=enable; 0=disable
171 12/24-Hour Time Stamp (0=12 hr; 1=24 hr)
172 Printer On-line (0=disable; 1=enable)
173 Enter 0 for 1200 Baud Rate
NOTE: For Event Log Report Codes program
System Group #2 in the #93 Menu Mode.
Programming for Access Control
VistaKey
See the VistaKey-SK Installation and Setup Guide for
the detailed programming instructions.
VistaKey Dialer Enables
When the VistaKey is installed with an alarm system,
the system defaults are set so that the system does not
send reports to the central station. The programming
is accomplished in field 135 for the following events:
ACS Troubles - To enable or disable ACS trouble
reporting.
ACS Bypasses - To enable or disable ACS bypass
reporting.
ACS System - To enable or disable ACS system
reporting, (i.e., ACS module reset).
ACS Alarms - To enable or disable ACS alarm
reporting.
Dialer (Trace) - To enable or disable access
grant/denial events sent to the central station.
PassPoint
The PassPoint ACS can dedicate some of its inputs for
use as regular VISTA-128BP/VISTA-250BP hardwired
zones (the zone response type is ACS). The PassPoint
ACS can also utilize the control panel dialer for reports
to the central station.
PassPoint Dialer Events
All PassPoint ACS events can be sent to the VISTA-
128BP/VISTA-250BP dialer via the VGM. These events
will also be logged into the control’s event log. This is
enabled in the PassPoint ACS. See the PassPoint ACS
documentation for a detailed explanation.
Programming the VISTA Gateway Module
See the PassPoint ACS instructions to program the
VISTA Gateway Module.
Using ACS Zone Inputs
If the PassPoint ACS has uncommitted zones, these
may be used by the VISTA-128BP/VISTA-250BP as
hardwired zones. To program for ACS zone inputs,
perform the following steps:
Step Action
1 Enter Zone Programming in the #93 Menu
Mode.
2 Program this zone as any other zone. Indicate
the input type as ACS (10).
3 Enter the PassPoint ACS’s zone ID (00-31)
See Zone Programming in the Programming Guide for
a detailed explanation.
Access Control of an Entry/Exit Point
The control can send entry and exit requests to the
VistaKey or PassPoint ACS utilizing keypads and
button-type (BR) RF transmitters. A zone is
programmed with a response type 27 (Access Point)
and an appropriate input type (console, RF).
Using the Alpha Keypad
Step Action
1 Enter Zone Programming in the #93 Menu
Mode.
2 Program the zone with a response type 27
(Access Point).
3 Enter the access point number (00-31) of the
door.
4 Program whether this is an entry or exit
point.
5 Enter the partition number.
6 Enter the input type as CS (09).
7 Enter the keypad ECP address.
See Zone Programming in the Programming Guide for
a detailed explanation.
Using Wireless Keypads
Wireless keypads (5827 & 5827BD) can provide
another way of entering or exiting the premises. They
Page view 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76 ... 146 147

Comments to this Manuals

No comments

InSinkErator SS-50 podręczniki

Instrukcje obsługi i podręczniki użytkownika dla Ekwipunek InSinkErator SS-50.
Dostarczamy 1 pdf podręczników InSinkErator SS-50 do pobrania za darmo według typów dokumentów: Instrukcja Użytkownika






Więcej produktów i instrukcji dla Ekwipunek InSinkErator

Modele Rodzaj dokumentu
LC-50 Instrukcja Użytkownika   InSinkErator LC-50 User Manual, 13 strony
WX-300 Instrukcja Użytkownika   InSinkErator WX-300 User Manual, 30 strony
F-C1100 Cold Only Faucet Instrukcja Użytkownika     InSinkErator F-C1100 Cold Only Faucet User Manual, 20 strony