ADEMCO Vista-128FB Setup Guide Page 63

  • Download
  • Add to my manuals
  • Print
  • Page
    / 147
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 62
4-1
SECTION 4
Programming
••••••••••••••••••••••••••••••••••••••••••••••••
NOTE: All references in this manual for number of zones, number of user codes, number of access cards,
and the event log capacity, use the VISTA-250BP’s features. See SECTION 1: General Description for the
table listing the differences between the VISTA-128BP and the VISTA-250BP control panels.
Program Modes
There are two programming modes for the VISTA-
128BP/VISTA-250BP. These are the Data Field
Program Mode and the #93 Menu Mode. The Data
Field Program Mode is where many system options are
programmed. The #93 Menu Mode is an interactive
mode that requires a 2-line alpha keypad (6139/6160).
The factory-loaded defaults (97) enable
keypad addresses 00-01 only. A keypad set to
one of these addresses must be used to
program the system initially.
Local keypad programming can be disabled
through Compass downloading software. If
this is done, Program mode can only be
accessed via the downloading software.
Entering and Exiting Programming Mode
Enter Programming mode using either method a or b:
a. Press both the [] and [#] keys at the same time
within 30 seconds after power is applied to the
control.
b. Enter the Installer Code + [8] + [0] + [0] + [0]
keys. The factory installer code can be changed
once in the Program mode (field 00).
NOTE: The default for the Installer Code is 4140.
Exit the Programming mode by either method a or b:
a. Press [] + [9] + [8]. Exiting by this method
prevents the installer code from being used to re-
enter Programming mode. Only method “a” can be
used to re-enter Programming mode.
b. Press [] + [9] + [9]. Exiting by this method
permits the installer code to be being used to re-
enter Programming mode.
Data Field Programming Mode
In the Data Field Program Mode you may access any
field simply by entering either [] or [#] + the field
number:
To write or change information in a field press []
+ the field number (03).
To read the information in a field press [#] + the
field number (#03).
When the entries for a field are completed, the keypad
beeps three times and advances to the next field.
Summary of Data Field Programming Commands
91
Select partition for programming partition-specific fields
92
Display the software revision level of the control panel
93
Enter Menu mode programming
94
Go to next page of fields
99
Go back to previous page of fields or exit Programming
Mode with no installer code lockout
98
Exit Programming Mode with Installer Code lockout
Moving Between Programming Levels
The data fields are grouped into three levels (referred
to as “pages”). The first page is accessed as soon as
Programming Mode is entered.
The second and third pages of data fields are indicated
at the keypad by a 1 and 2, respectively, in front of the
2-digit field address. “ALT PROGRAM MODE” is
displayed along with a “100” or “200,” indicating which
page of program fields is accessed.
To access the next level of programming fields,
perform the following steps:
Step Action
1
Press 94.
2 Press [] + [XX], where XX = the last two
digits of the program field, and make the
desired entry.
NOTES:
Press 94 to move to 2
nd
page, (fields 101 - 176);
press 99 to move back to 1
st
page.
Page view 62