Section 22 – Data Field Descriptions
22-17
2*21 SUPERVISION PULSES FOR LRR [000]
| |
F B S
Used for supervised connection to 7920SE.
Enter 1 to enable pulses for each type of LRR trigger (Fire, B
urglary/Audible Panic,
Silent Panic/Duress. This option causes the control to send periodic short pulses on the
J7 radio triggers. These pulses are used by the 7920SE to determine that its connection
to the control is still intact.
Enter 0 if not desired.
Must be 1 for UL commercial burglary installations.
2*22 DISPLAY FIRE ALARMS OF OTHER PARTITIONS (partition-specific)
[0]
Enter
1
to allow fire alarms that occur on other partitions to be displayed at this
partition's keypad(s). Otherwise, enter
0
.
2*23 DISPLAY BURG & PANIC ALARMS OF OTHER PARTITIONS
[0]
Enter
1
to allow burglary and panic alarms that occur on other partitions to be
displayed at this partition's keypad(s). Otherwise, enter
0.
2*24 DISPLAY TROUBLES OF OTHER PARTITIONS
[0]
Enter
1
to allow troubles that occur on other partitions to be displayed at this partition's
keypad(s). Otherwise, enter
0
.