ADEMCO VISTA-128B Setup Guide Page 251

  • Download
  • Add to my manuals
  • Print
  • Page
    / 252
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 250
¬.l
K3271 7/98
++
-
N.C.
N.C.
N.O.
2k EOLR
(note 1)
2k EOLR
(note 1)
+-
+
-
+
-
BELL
SIREN
NO CONNECTION
TRANSFORMER
16.5VAC, 40VA
ADEMCO No.1361
(IN CANADA
USE No. 1361CN)
or 4300 IF
X-10 DEVICES
WILL BE USED
Connect to
24hr. 120VAC,
60 Hz Outlet
Red Blk Grn Yel
REMOTE KEYPAD
Use 4137AD/6137/6128
5137AD/6139
(Addressable keypads) only
++
-
N.C.
N.C.
2k EOLR
(note 1)
2k EOLR
(note 1)
++
-
N.C.
+
+
-
N.C.
N.C.
2k EOLR
(note 1,4)
TIP
(BROWN)
RING
(GRAY)
TIP
(GREEN)
RING
(RED)
Handset
Incoming
Phone Line
Telephone connections
using Ademco No. 620
RJ31X direct connect
cord.
EARTH GROUND
Connect to good earth
ground to maintain im-
munity to transients.
See Instructions for
proper grounding.
SMOKE
4190
RPM
4278
PIR
Polling loop rating: 128mA max. See
Installation Instructions for maximum
number of devices supported and
maximum wire run length
VISTA-128B
SUMMARY OF CONNECTIONS
USE UL LISTED ENERGY CABLE FOR ALL CONNECTIONS
Zone resistance (Excluding EOLR):
ZONE 1,8: 100 OHMS MAXIMUM
ALL OTHER ZONES: 300 OHMS MAXIMUM
ZONE 1
ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9
2-WIRE SMOKE
DETECTOR LOOP
(Also supports NO/NC Burg contacts)
POLLING LOOP
Programmable Response
(Fast/Normal) Loop
LATCHING TYPE GLASS
BREAK DETECTOR LOOP
Data in
Data out
12345678910 11121314151617181920 212223242526
27
28 29 30
RED (+)BLK (-)
Connect to
12VDC, 4AH
or 12VDC, 7AH
GEL CELL
BATTERY
CHARGING
VOLTAGE
13.7VDC
See
Installation
Instructions for
required
capacity
Replace
every
3 years
NOTE:
WHEN POWERING UP
THE PANEL, PLUG THE
TRANSFORMER IN BEFORE
CONNECTING THE BATTERY.
See Installation Instructions
for max # of keypads
and for max wire run length.
ALARM SOUNDER OUTPUT 10VDC - 13.8VDC
AUXILARY POWER OUTPUT
9.6VDC - 13.8VDC,
750mA maximum
Note: Include current drawn
by keypads and polling loop
devices when making
auxiliary power calculations.
+
-
NOTES:
1. Zone 1 may be selected for EOLR supervised
or normally closed (no EOLR) operation via
cut jumper. (Cut red jumper for normally closed
operation. Do not cut for Fire Usage). Zones 2-8
may be selected for either operation via program
field *41.
Zone 1 supports 2-wire smoke detectors.
See Installation Instructions for recommended type
and maximum number of detectors supported.
2.
Zone 7 may be used for remote keyswitch arming/disarming.
See Installation Instructions for wiring instructions.
3.
Zone 8 supports 2-wire latching type glass break detectors.
See Installation Instructions for recommended type and
maximum number of detectors supported.
4.
1 2 3 4 5 6 7 8 9
1. Not Used
2. Ground-
3. Out 1 (Ground Start)
4. Ground-
5. Out 2 (fire)
6. Ground-
7. Out 3 (burg/aud. panic)
8. Ground
9. Out 4 (silent panic/
duress)
Optional programming:
Out 1: Open/close or keypad-like sounding
Out 2: Armed LED
Out 4: Ready LED
Ratings for Out 1:
Active: 10VDC-13.8VDC through 4k OHMS
Not Active: 100 OHMS to ground
Ratings for out 2-4:
Active: 10VDC-13.8VDC through 5k OHMS
Not Active: 1k OHMS to ground
N.C.
N.O.
N.O. N.O.
2k EOLR
(note 1,2)
N.O. N.O.
N.O.
N.C.
N.O.
2k EOLR
(note 1)
2k EOLR
(note 1,3)
N.C.
+
-
J7
GLASS
BREAK
1 2 3 4 5 6 7 8 9
J8
MAKE CONNECTIONS USING
No. 4142TR CABLE
WARNING: OWNER'S INSTRUCTION NOTICE NOT TO BE REMOVED
Fire
Usage
Burg.
Usage
CONNECTION OF THE FIRE ALARM SIGNAL
TO A FIRE ALARM HEADQUARTERS OR A
CENTRAL STATION SHALL BE PERMITED
ONLY WITH THE APPROVAL OF THE LOCAL
AUTHORITY HAVING JURISDICTION. THE
BURGLAR ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY
NUMBER.
1. In 2 (Printer DTR)
2. Ground
3. In 3 (4300 sync)
4. In 4 (4300 sync)
5. Ground
6. Out 5 (4300 data)
7. Out 6 (Printer RXD)
8. Ground
9. Ground
Red Jumper
(note 1)
DOC LOAD NO.: 5
J7 Header J8 Header
BATTERY
TABS
4192SD
SMOKE
WARNING: TO PREVENT
RISK OF ELECTRICAL
SHOCK, DISCONNECT
TELCO JACK BEFORE
SERVICING THIS PANEL.
THIS EQUIPMENT SHOULD BE INSTALLED
IN ACCORDANCE WITH THE NATIONAL
FIRE PROTECTION ASSOCIATION'S
STANDARD 72 (NATIONAL FIRE
PROTECTION ASSOC., BATTERYMARCH
PARK. QUINCY, MA. 02269). PRINTED
INFORMATION DESCRIBING PROPER
INSTALLATION, OPERATION, TESTING,
MAINTENANCE, EVACUATION PLANNING
AND REPAIR SERVICE IS TO BE
PROVIDED WITH THIS EQUIPMENT.
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS SYSTEM.
Zone response time:
ZONES 1-8: 350mSec-500mSec
ZONE 9: Programmable for
Fast: 10mSec-15mSec
Normal: 350mSec-500mSec
(default response)
COMPLIES WITH FCC RULES, PART 68
FCC REGISTRATION NO. AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B
THIS DEVICE COMPLIES WITH PART 15 OF
FCC RULES. OPERATION IS SUBJECT TO THE
FOLLOWING TWO CONDITIONS: (1) THIS DEVICE
MAY NOT CAUSE HARMFUL INTERFERENCE, AND
(2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE
RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
(Refer to Installation Instructions for information concerning Direct Wire
Downloading and printer connections using the 4100SM Serial Module.)
Notes For UL Household Fire Installations
1. Use 12VDC, 14AH battery
2. Maximum auxiliary current,
including polling loop 300mA
3. Combined alarm and auxilary power output
and polling loop current must be limited to 750mA
for UL985 Household Fire Installations.
ALL CIRCUITS ARE
POWER LIMITED.
Blue
Jumper
(note 5)
5. Cut blue jumper to disable supervision of alarm sounder output.
Leave jumper intact to supervise output. (See Installation
Instructions for Programming and Wiring Instructions).