Section 2 Installing the Control & Peripherals
2-7
Installing the 5881/5882 Receiver
RF System Installation Advisories
Follow the guidelines below when installing the RF
receiver. (Disregard
if the receiver is mounted in the
control cabinet.)
Place the RF receiver in a high, centrally located area
for best reception.
Do not locate the receiver or transmitters on or near
metal objects. This decreases range and/or blocks
transmissions.
Do not locate the receiver in an area of high RF
interference (revealed by frequent or prolonged
lighting of the LED in the receiver; random flicker is
OK).
TO CONTROL'S REMOTE KEYPAD
CONNECTION POINTS. EACH RECEIVER
MUST BE ON INDIVIDUAL HOME RUN.
USE MAX. of 220 ft. [67m of #22 (0.64mm)
WIRE or 550 ft. (168m) of #18 (1mm) WIRE
FOR EACH RUN]. OBSERVE 20 ft. MAX.
FOR COMMERCIAL FIRE INSTALLATIONS.
(SEE RECEIVER'S INSTRUCTIONS.)
DIP SWITCH WHITE AREAS = SWITCH
HANDLES. POSITIONS 2-4 DETERMINE
RECEIVER'S ADDRESS. CONSULT
CONTROL'S INSTRUCTIONS FOR
ADDRESS TO USE. DIP SWITCH BELOW
SHOWN SET FOR ADDRESS "0."
SWITCH
POSITION
RECEIVER ADDRESS SETTINGS
(" - " MEANS OFF)
0 1 2 3 4 5 6 7
4
3
2
1
5
PRESENT ONLY ON 5881EH (SEE TEXT AT LEFT)
ON ON ON
ONON
ONON ONON
ONON
ON
FOR FUTURE USE
DIP SWITCH #5 (PRESET ONLY ON 5881EH)
ON: SETS 5881EH FOR USE IN COMMERCIAL
FIRE APPLICATIONS (SEE THE RECEIVER'S
INSTRUCTIONS)*.
OFF: USE IN NON-COMMERCIAL FIRE
INSTALLATIONS.
* FOR COMMERCIAL FIRE APPLICATIONS
THE 5881EH PC BOARD MUST BE MOUNTED
IN A SEPARATE CABINET (SEE RECEIVER'S
INSTRUCTIONS FOR DETAILS).
MOUNTING
HOLES
INSERT IN
RIGHT-HAND
TERMINALS
CIRCUIT
BOARD
DIP SWITCH
YELLOW
RED
BLACK
GREEN
INTERFERENCE
INDICATOR LED
WIRING
OPENING
PLUG & SOCKET
ANTENNAS
Figure 2-9. 5881/5882 RF Receiver
The RF receiver must be at least 10 feet from any
remote keypad to avoid interference from the
microprocessors in those units.
Installation and Setup of the 5881/5882 Receiver
T
o install the receiver, perform the following steps and
refer to Figure 2-9:
1. Set the receiver's DIP switches for device address 0,
(all switches are in the OFF position).
2. Mount the receiver. The RF receiver can detect signals
from transmitters within a nominal range of 200 feet.
Take this into consideration when determining
mounting location.
3. Connect the receiver's wire harness to the control's
keypad terminals (4, 5, 6, and 7). Plug the connector
at the other end of the harness into the receiver.
4. Refer to the installation instructions provided with
the receiver for further installation procedures
regarding antenna mounting, etc.
In Canada
, 5800 systems must use 5882
Series receivers. Information relative to the
5881 Series of receivers applies as well to the
5882 Series. 5881 and 5882 Series receivers
can support the same 5800 type transmitters.
Any zone
number
from 1025 can be used as
a 5800 Series wireless zone.
Jam Detection and Reporting
When field
22, option 4 (RF SYSTEM) is selected, a
5800 Series receiver detecting a jam condition sends an
E344
(RF Receiver Jam Detect) Contact ID
®
report to the
central station. At the same time, a
Rcvr Jam
(on alpha
keypads) or
CHECK 90
(on fixed-word keypads) message
alternates with the present system message on the
keypad.
When the jam condition is cleared, a
Restore
message is
sent to the CS. Entering a code and OFF restores the
keypad display.
The default for this option is 0 (disabled).
U
L
RF Jam Detection must be enabled for UL
installations using wireless devices.
Note:
when RF jam detection is selected, an RF receiver
will detect a condition that may impede proper RF
reception (i.e., jamming or other RF interference). Such a
condition will produce a message display, and a report
will be sent to the central monitoring station (if trouble
reporting is enabled).
Normal use of a 5827 wireless keypad may
cause a false RF jam message to be displayed
in systems that have been programmed for RF
Jam Detection.
Receiver Supervision
The receiver is supervised. The following conditions cause
a Trouble report to be generated and
CHECK
and
ZONE
09
messages to be displayed:
Communication between the panel and the receiver is
interrupted.
or
No valid RF signals from at least one supervised
wireless transmitter are received within 12 hours.
House Identification
If you are using a 5804BD, 5827, or 5827BD Wireless
Keypad with the system, you must program a House ID
Code (01-31) in field
24 to establish proper
communication. The keypad must be set to the same ID.
House ID set to 00 disables
all
wireless keypads.