Additional Features:
Basic Hardwired Zones
Provides nine style-B hardwired zones with the
following characteristics:
• EOLR supervision (optional for zones 2-8) supporting N.O. or
N.C. sensors (EOLR supervision required for fire and UL
burglary installations)
• Individually assignable to one of 8 partitions
• Up to 16 two-wire smoke detectors on zone 1
• Four-wire smoke or heat detectors on zones 1-8 (power
to four-wire smoke detectors must be supervised with
an EOL device)
• Up to 50 two-wire latching glassbreak detectors on
zone 8
Polling Loop Expansion
Supports up to 119 additional zones using a built-in polling
(multiplex) loop interface. Current draw can total up to 128mA.
Polling loop zones have the following characteristics:
• Must use RPM (Remote Point Module) devices
• Supervised by control panel
• Individually assignable to one of eight partitions
Wireless Expansion
Supports up to 128 wireless zones using 5881RF Receiver
(fewer if using hardwire and/or polling loop zones). Wireless
zones have the following characteristics:
• Supervised by control panel for check-in signals (except certain
nonsupervised transmitters)
• Tamper protection for supervised transmitters
• Individually assignable to one of eight partitions
Scheduling
Provides the following scheduling capabilities:
• Open/close schedules (for control of arming/disarming and
reporting)
• Holiday schedules (allows different time windows for
open/close schedules)
• Timed events (for activation of relays, auto-bypassing and
unbypassing, auto-arming and disarming, etc.)
• Access schedules (for limiting system access to users by time)
• End user output programming mode (provides
20 timers for relay control)
Eight Partitions
Provides the ability to control eight separate areas independently,
each functioning as if it had its own separate control. Partitioning
features include:
• A Common Lobby partition (1-8), which can be programmed to
arm automatically when the last partition that shares the
common lobby is armed, and to disarm when the first partition
that shares the common lobby is disarmed
• A Master partition (9), used strictly to assign keypads for the
purpose of viewing the status of all eight partitions at the same
time (master keypads)
• All zones assignable to one of eight partitions
• Keypads assignable to one of eight partitions or to Master
partition 9 to view system status
• Ability to assign relays to one or all eight partitions
• Ability to display fire and/or burglary and panic and/or trouble
conditions at all other partitions’ keypads (selectable option)
• Certain system options selectable for each partition, such as
entry/exit delay and subscriber account number
4293SN
Adapters
Notification
Appliances
VISTA-128BP
4101SN
Relay
Module
9500SN
Glassbreak
4208U
Eight-Zone
Expansion
Module
710
Light
748
Horn
PassPoint
5881
Wireless
Receiver
6139
Custom Alpha
Console
4204
Relay
Module
4204CF
Supervised
NAC
Module
Phone Line to Central Station
7845C Cellular
7820 Radio
or
Notification Appliances
Keyswitch
Option
416
5192
Series Smoke
Detectors
998MX
Dual
Fresnel PIR
4278EX
Quad PIR
4208U
Eight-Zone
Expansion Module
V-PLEX Loop
VGM (PTVGM)
VISTA
Gateway
Module
Alpha Paging
Module
Parallel Printer
Serial Printer
RS232
Q2260SN
Multiplex
DUAL TEC
®
Motion
Detector
ADEMCO VISTA-128BP
128 Zone UL Commercial Burglary Control Panel
Page view 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 79 80

Comments to this Manuals

No comments