FEATURES:
Honeywell’s 4208U Remote Point Module (RPM) is an eight-zone expander
that allows the use of available expansion zones on ADEMCO controls that
support V-Plex polling loop devices.
• Can be optionally powered from an external DC power supply to
reduce the amount of current draw from the polling loop
• Uniquely identifies eight EOLR supervised zones (all zones use
10K resistors, supplied)
• DIP Switches can be used to set zone numbers or serial numbers
• When used in the serial number mode, each serial number in the selected group can be
assigned to any zone number
• Loops A & B can be programmed for fast (10msec) response
• Provides cover tamper protection, which may be enabled or
disabled via on-board DIP Switches
SPECIFICATIONS:
Power Input Source
(Input Voltage: 11-14VDC)
Current Draw (all zones shorted)
From Polling Loop From External Power
Polling Loop Only 27.3mA N/A
Polling Loop and 0.6mA 33mA
External Power Input
For UL Listed Commercial Fire Usage:
Use N.O. contacts. Style B supervise these loops using Model #EOL 100 fire listed 10K EOLRs
(purchased separately).
For UL Listed Commercial Burglary Usage:
Use N.O. or N.C. contacts. Supervise using EOLRs supplied.
ORDERING:
Part No. Description
4208U
8 Zone
Expander
Physical:
• 6-7/16” W X 4-1/4” H X 1-1/4” D
(163mm X 108mm X 32mm)
Electrical
• Polling Loop input: 7.3 - 14VDC range
• Current draw: 28.6mA max. External power and polling loop
See chart below.
External Power Input (optional)
• 12VDC @ 28mA (from control panel’s auxiliary power)
Sensor Loop Response:
• Slow: 400 msec (all loops)
• Fast: 10msec (option for loops A and B)
Sensor Loop Current:
• Polling loop input = 11VDC, no external power input):
• 0.52mA (normal)
• 1.3mA (shorted)
Sensor Loop Max. Current:
• Up to 300 ohms of wire resistance + 10K EOLR
Agency Listings
UL 985 Household Fire
UL 1023 Household Burglary
UL 609 Commercial Burglary
UL 864 Commercial Fire
CSFM
FM
CUL
CE (requires #N6361)
4208SN
V-Plex Zone Expander