69
7830R
AlarmNet-M Transceiver
SPECIFICATIONS:
ORDERING:
The 7830R is wired to the panel per wiring diagram provided
with the radio. Observe the LED once the 7830R is in normal
operating mode to determine optimal installation location via
built in diagnostics of the 7830R. Can be mounted vertically or
horizontally depending on which antenna is used. Radio should
not be mounted where it would be obstructed by a steel
structure such as security doors and windows which may be
pulled down at night. Once the radio has been installed and
tested, it must be registered with AlarmNet before it can be
monitored. NOTE: No alarm traffic will be routed to the
monitoring central station until the 7830R completes the
registration process.
ACCESSORIES
Cables
• 7626-5, 7626-12, 7626-25HC, 7626-50HC
Antennas
• 7625-3DB - 3dB gain antenna
• 7674 - directional antenna (6dB)
• 7674-13-directional antenna (13dB)
• 7825 - weatherproof outdoor antenna
• 7825MB - Mounting bracket for 7825 antenna
• 7825DP - dipole antenna for vertical mounting
Miscellaneous
• 1361 - transformer (required for operation)
• 7720BT- battery (required for operation)
Programmable Features
EEROM (Electrically Erasable ROM) technology allows the
7830R to be programmed via the AlarmNet 7720P
programmer.
Programmable features include
• Daily supervision ON/OFF
• Tamper reporting ON/OFF
• Opening/closing reports ON/OFF
• Telco line fault report ON/OFF
• DC loss report ON/OFF
• Zone delay for each of 4 zones
• Voltage trigger input, inverted or non-inverted
• Dry contact input, normally open or normally closed
• Pulsed or non-pulsed for each zone (alarm trigger from bell
output to differentiate Burg/Fire
• Fault relay ON/OFF
• Fault relay latch ON/OFF
• Dual Central Station reporting
MECHANICAL
Dimensions
• 8.5" x 9.5"'x 1.7" (without antenna or RF connector)
Operating Temp
• -30° to +60° C
Storage Temp
• -40° to +70° C
Humidity
• 5% to 95%, non-condensing
Altitude
• To 10,000' operating
ELECTRICAL
Power
• 16.5VAC 40VA transformer
Battery Backup
• 12V 0,8Ah rechargeable sealed lead acid battery
Current Drain
• 130 mA average
Input Trigger Levels
• Gate "O"' level less than 1.5V, "I" level greater rate than
3.5V, Sense of 4 zones, may be inverted in groups of 2
TRANSMITTER
RF Power Output
• 2 watts maximum
Frequency Stability
• ±1.5 ppm
Frequency Bond
• 896-902 MHz Transmit 935-941 MHz Receive
Channel separation
• 12.5 kHz
Modulation Modified
• Modified GMSK 8kbps data rate
Receiver Sensitivity
• 113 dBm
Regulatory Approvals
• FCC90-UL, ULC
Radio Fault Output
• Form C relay (can be programmed for fail-safe if desired)
Part No. Description
7830R Subscriber Transceiver
7830RCN Subscriber Transceiver (Canada)
Ask your provider for the AlarmNet technology used in your area.
C
I
A
M
AlarmNet-A Original AlarmNet
AlarmNet-M Mobitex System
AlarmNet-C Control Channel Cellular
AlarmNet-i Internet
AlarmNet Services
Comments to this Manuals