FEATURES:
• Can be used on controls that support up to 250 zones
• Provides up to six Class B supervised zones using external
10k EOL resistors and two Class A supervised zones using
built-in 10k EOL resistors
• Powered from addressable loop or optionally powered from an
external DC power supply to reduce current draw from the
addressable loop
• Each zone is identified by a unique serial number, which is
assigned via on-board DIP switches
• Detects faults an all zones with 400msec of occurrence. Two
Class B zones can be optionally set for fast (10msec)
response via on-board DIP switches
• Provides cover tamper protection, which may be enabled or
disabled via on-board DIP switches
Class B to Class A Zone
Converter Features
• Allows up to two Class B control panel zones to be converted
into Class A zones
• Control panel’s response time to faults on the module’s Class
A zones is equal to the response time of the control panel’s
converted Class B zones plus one msec
• Must be powered from an external 12vdc power supply such
as the 12v auxiliary power output on the control panel
Honeywell’s 4208SNF Remote Point Module
(RPM) is a UL listed eight-zone expander
that provides (6) class B and (2) class A
expansions zones to any Vista Fire/Burg
control panel that supports serial V-Plex
polling loop devices.
4208SNF
UL Listed V-Plex Zone Expander