ADEMCO VISTA-100 Service Manual Page 67

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 66
67
7720ULF
UL Listed Radio Transmitter
SPECIFICATIONS:
ORDERING:
Installation:
The 7720ULF should be mounted indoors, in an area that is
easily accessible. Before mounting the panel to the wall, the
best location to install the panel can be determined by use of
the 7715DF installation tool. If it is necessary to remotely
mount the antenna avoid obstructions such as metal ducts,
pipes, foil backed insulation, etc. as these will adversely affect
Transmission. When mounting the antenna remotely, the
coaxial cable must be inside conduit.
ACCESSORIES
Cables
7626-5, 7626-12, 7626-25HC, 7626-50HC
Antennas
7625-3DB - 3dB gain antenna
7674 - directional antenna (6db)
7674-13 - directional antenna (13dB)
7825 - weatherproof outdoor antenna
7825MB - Mounting bracket for 7825 antenna
7825DP - dipole antenna for vertical mounting
Miscellaneous
7620TR - transformer (required for operation)
Programmable Features
EEROM (Electrically Erasable ROM) technology allows the
7720ULF to be programmed via the 7720P programmer.
Programmable features include
Both the open loop supervision normally closed and the fire
loop can be programmed for an open to signal trouble or a
short to signal alarm
Class A or B fire. Supervisory and waterflow functions are
programmable for 0-90 second delays, in one-second
increments.
AlarmNet or private network reception
True restore
Voltage trigger input, inverted or non-inverted
Dry contact input, normally open or normally closed
Slave mode to existing fire control using telco, alarm
open/close and test inputs
Bell supervision
Ground fault supervision
Bell pulsed
Bell time-out, 0-30 minutes in 2-minute increments
ELECTRICAL
Power
18.5VAC 40VA transformer
Battery backup
12V 0.8Ah rechargeable sealed lead acid battery
Current drain
100mA standby; 900mA in alarm
Input trigger levels
3.7 to 14 volts into 2K ohms
MECHANICAL
Dimensions
12" W X 12" H X 4" D
Operating Temperature
0° to +50° C
Storage Temp.
-40° to +70° C
Humidity
90% non-condensing
Altitude
To 10,000’ operating, 40,000’ storage
TRANSMITTER
RF power Output
5 watts nominal
Frequency Stability
±5 PPM
Frequency Band
928.0125 MHz to 928.3375 MHz,
935-941 MHz Receiver
Channel Separation
25 kHz
Antenna
Female N-Type connector
Receiver Sensitivity
-113 dBm
Regulatory approvals
FCCID: CFS7720
Radio Faults Output
Form C Relay
CONTROL
Aux. Power Output
150 mA max
Alarm Sounder
Style Y (Class B)
Polarized Bell
500mA max
Backup Battery
12VDC, 7AH NP7-12
Standby
24 hours with max 400mA aux. Loading
Zones
Two style D (Class A) 6 style B (Class B)
Listings and Approvals
UL, FM, MEA, CFM
Part No. Description
7720ULFPLUS Transmitter
Contact your local distributor for the channel used in your area.
Page view 66