ADEMCO VISTA-100 Service Manual Page 49

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 48
49
VistaView-100
CCTV Switcher
General Information:
The ADEMCO VistaView-100 module is a CCTV switcher that
accepts 4 video inputs, switching them to 2 video outputs. The
video inputs are compatible with any standard 75 ohm,
line-locked, black and white or color video camera. The video
outputs are compatible with any standard 75-ohm video
monitor or recorder. The VistaView-100 module also provides
a form-C trigger relay output and an open collector video loss
output. The trigger relay output may be used to start and stop
recording or to change from time lapse to real time recording.
The video loss output indicates when video signals are no
longer present on one or more video inputs.
VistaView-100 has two modes of operation. In normal
sequencing mode, VistaView-100 automatically sequences the
installer selected video inputs to the 2 outputs using an
installer selected dwell time that is common to both outputs.
This mode allows cameras assigned to a given output to be
continuously monitored using a video monitor and/or
continuously recorded using a recorder set for time lapse
recording. In panel trigger mode, VistaView-100 switches one
specific video input to the OUTPUT1 line on a momentary
basis using a separate installer selected dwell time or on a
latched basis as directed by commands received from an
ADEMCO control. VistaView-100 receives these commands
via the control panel’s ECP bus and responds to the same
commands that the panel uses to activate the relays on the
4204 relay module, thereby allowing it to be used with any
panel that supports the 4204. This mode allows one specific
camera to be monitored by a video monitor and/or recorded
by a recorder set for real time recording when an installer
defined event occurs such as an alarm or trouble condition on
a selected control panel zone.
VistaView-100 can be powered from a control’s 12VDC
auxiliary power Output or from a supplementary 12VDC power
supply. The VistaView-100 module can be used without a
control when powered by a supplementary 12VDC power
supply and when the panel trigger mode will not be used.
The VistaView-100 module provides BNC connectors for
video input and output connections and screw terminals for
power source. ECP bus, trigger relay, and video loss
output connections.
Installation:
The VistaView-100 may be wall mounted or placed on a shelf.
The VistaView-100 is supplied in a plastic case. To mount the
case on a wall, insert two self-tapping screws (supplied) into
the wall with the screw heads projecting approximately 1/8
inch. Remove the VistaView-100 PCB from the case and with
the holes for the BNC video connectors facing down, position
the slotted holes on the case back onto the screw heads. On
the inside of the case remove the plastic step that covers the
screw heads and tighten the screws to secure the case to the
wall. Install the VistaView-100 PCB into the case.
Connections:
The VistaView-100 must be connected via its video BNC
connectors to the video cameras, monitors, and recorders to
be used with 75 ohm coaxial cable. Consult the instructions
provided with these devices for cable length limitations.
Depending on the devices used, the maximum cable length
running from a camera, through VistaView100, to a monitor or
recorder is typically 500 to 1000 feet when high quality, low
distortion coaxial cable such as RG59B/U is used. Run wires
from VistaView-100’s power input and ground screw terminals
to a 12VDC power source (i.e., control’s auxiliary power
output). If panel trigger mode will be used, run wires from
VistaView-100’s Data In/Out screw terminals to the
corresponding ECP bus terminals on the control. If video
loss is to be annunciated on the control, run a wire from the
video loss screw terminal to one leg of the EOL resistor on
a control panel zone that has a grounded return. Program
the zone for 24-hour trouble (or equivalent) response.
When the VistaView-100 is not powered from the control,
run a wire from its ground screw terminal to a ground
terminal on the control so that both devices share a
common ground reference.
Programming and Operation:
For normal sequencing mode, set the DIP switches OUT1 and
OUT2 to assign the desired video inputs to OUTPUT1 and
OUTPUT2, respectively. Adjust the NSD trimpot to select the
desired normal sequencing dwell time (1 to 30 seconds).
Note that the VistaView-100’s trigger relay remains inactive in
this mode.
For panel trigger mode, set the ECP DIP switch to the address
that will be used by the control to communicate with the
VistaView-100. Refer to the instructions provided with the
control when selecting this address. The table below shows the
DIP switch settings for each of the 16 possible addresses that
can be selected. Be sure to choose an address that is different
from the addresses of all other devices, including other
VistaView-100 modules, which are connected to the Control’s
ECP bus.
Program the address selected into the control and assign
device type 4 (i.e., output device) to this address using the
control’s Device Programming Menu. Also program the events
that will trigger relay numbers 1 through 4 (corresponding to
INPUT1 through INPUT4) along with start and stop options for
these relays using the control’s Relay Programming Menu.
Video inputs should either be assigned an “Activate For 2
Seconds” start option (this option does not require a stop
option to be programmed) or an “Activate Steady Until
Stopped” start option (this option requires a stop option to be
programmed). When VistaView-100 receives a command to
activate a relay for 2 seconds, it will switch the corresponding
video input to OUTPUT1 for the dwell time selected by the
PTD trimpot. This dwell time ranges from 2 to 60 seconds.
Adjust the PTD trimpot to select the desired dwell time. When
VistaView-100 receives a command to activate a relay steady,
it will switch the corresponding video input to OUTPUT1 until it
receives another command to deactivate the relay. When
VistaView-100 receives a command to activate a second,
third, or fourth relay before a previously switched input has
been deactivated, it will automatically sequence between all
activated inputs using a fixed 1-second dwell time.
VistaView-100 will activate its on-board trigger relay when one
or more inputs are switched to OUTPUT1 and will de-activate
this relay when all inputs have been deactivated.
Page view 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 79 80

Comments to this Manuals

No comments