System Programming - Group #6 Confirm Options (DD243)
These options allow the confirmed alarm reporting operation to be modified to taylor
the system to requirements of DD243: 2002, depending on the type of installation. The
default options should be used in all installations except where the installation uses
portable fobs to unset.
In programming mode:
The first two digits entered are #6 for Confirm Options
The third digit entered is the required confirm option (1-9)
The fourth digit entered is the option value.
Group #6 - Option 1 Report Confirmed Alarms
This dictates if and when a sequentially confirmed alarm report can be generated. A
sequentially confirmed alarm means that two separate alarm zones must be activated
during the set period within the confirmed alarm time window (See group 0). The
option has 4 settings:
0 No
No confirmed alarm signals will be generated
1 Before Entry
This option means that confirmed alarms can occur during the set state until a Final
Exit type zone it activated and the entry timer started. From that point on, no con-
firmed alarms can be generated until a user unsets then sets the system again.
2 Except Entry
This option means that confirmed alarms can be generated during the set state except
during the entry delay period. If a Final Exit type zone starts the entry timer, and then
an Entry timeout occurs, the confirmed alarm functionality will come back into
operation after the timeout has occurred.
3 Always
This option means that confirmed alarms can be generated by alarms occuring at any
time during the set state.
Group #6 - Option 2 Timeout Alarm Affect Confirm
This selects whether an Entry Timeout alarm will contribute to a confirmed alarm.
When enabled (1), a timeout alarm will contribute to a confirmed alarm. When
disabled (0), a timeout alarm will only cause an unconfirmed alarm. It will not be
counted as either the first or second contribution to a confirmed alarm.