VISTA-128FBP/VISTA-250FBP Installation and Setup Guide
4-4
MAIN MENU
OPTIONS
SCHEDULED CHK-IN
1 = YES 0 = NO 0
For defining the schedule for the system to automatically call the downloader.
Following is a list of commands used while in the Menu Mode:
#93 Menu Mode Programming Commands
#93
Enters Menu Mode.
[]
Serves as [ENTER] key. Press to have keypad accept entry.
[#]
Backs up to previous screen.
0
Press to answer NO.
1
Press to answer YES.
00, or 000+[]
Quits Menu Mode and goes back to Data Field Programming Mode, if entered at first prompt of each main menu option.
Zone Number Designations
The VISTA-128FBP supports up to 128 zones, the
VISTA-250FBP supports up to 250 zones, of hardwire,
polling loop and/or wireless protection, distributed
among up to 8 partitions. The following table lists the
zone numbers and the types of sensors that can be used
with each, and some alternate functions of the zones.
Zone
Function
1 & 2 2-wire Smoke Detectors (if used)
6 Cabinet Tamper/Ground Fault (if used)
7 Keyswitch (if used)
8 Latching-Type Glassbreak Detectors (if used)
1-8 Traditional Hardwired Zones
1-250 5800 Series Wireless Devices
9-250 Polling Loop Devices
995 + 1 Panic (Do not use in Fire Alarm applications)
996 # + 3 Panic (Do not use in Fire Alarm applications)
999 + # Panic (Do not use in Fire Alarm applications)
Zone Defaults
Zone # Zone Type Zone # Zone Type
001 09 800-830 00
002 09 970 19
003 03 971-974 19
004 03 975 00
005 03 988 & 990 00
006 03 992* N/A
007 03 995 00
008 03 996 00
009250 00 997 19
601-632 00 999 06
NOTES:
* Zone 992 is the Duress zone. Programming of the zone
response type is not applicable. This zone requires only the
report code programming.
Zone Index
The zones are designated as follows:
ZONE #
RANGE
ZONE
FUNCTION
ACTUAL ZONE
001 250 Protection
zones
As indicated
601 632 Relay
Supervision
Zones
6 + 2-digit Relay Number; e.g.,
Relay Number 03, if supervised,
is zone 603.
NOTE: Relay supervision
should be used only for
relays on 4204CF modules.
800 830 ECP Device
Supervision
Zones
8 + 2-digit Device Address; e.g.,
Device Address 01, if
supervised, is zone 801.
970-977,
988, 990, &
997
System
Supervision
Zones
970: Bell 1Output
971 Bell 2 Output
972 Earth Ground
973 J2 Input 1
(
communications
device)
974 Dialer 1
975 Dialer 2
976 Auxiliary Relay
977 J2 Trigger Outputs
988: 2
nd
Wireless Receiver
not receiving signals
990: 1
st
Wireless Receiver
not receiving signals
997: Polling Loop (short
circuit)
992, 995
999
Duress and
Keypad Panics
992: Duress
995: 1 + panic (A key)
996: 3 + # panic (C key)
999: + # panic (B key)
Supervision zones should be given a response type of either 05
(Trouble by Day, Alarm by Night) or 19 (24-Hour Trouble).