Section 5 – Data Field Descriptions
5-3
FIELD TITLE and DATA ENTRIES EXPLANATION
*23
Multiple Alarms (partition-
specific)
0 = disable
1 = enable
If enabled, allows more than one alarm sounding for a given zone during an
armed period. Pertains to Burglary zones.
NOTE: that multiple alarm soundings will not occur more frequently than
allowed by the programmed alarm sounder duration. This has no impact on
the number of communication messages transmitted.
Must be 1 for Commercial Fire and UL Commercial Burglary installations.
*24
Ignore Expansion Zone Tamper
0 = disable (tamper detection)
1 = enable (no tamper detection)
If disabled, the system monitors the tampers on expansion zones.
NOTE: Only applicable to certain polling loop sensors with tamper switches or
5800 Series transmitters.
Must be 0 for UL installations.
*25
Burglary Trigger for Response
Type 8
0 = disable
1 = enable
If enabled, allows triggering of the voltage output 3 on Pin 3 of the J2 header
to include zone response type 8 (24-hr. auxiliary).
*26
Intelligent Test Report
0 = disable
1 = enable
If enabled, no test report is sent if any other type of report was sent since the
last test report.
If disabled, test reports are sent at the set intervals, regardless of whether or
not any other report has been sent.
Must be 0 for Commercial Fire and UL Commercial Burglary installations.
*27
Test Report Interval
Enter 0001-9999 for the test report interval in
hours.
Enter 0000 for test reporting.
If a test report is desired, enter a test code in
Report Code Programming
in
#93 Menu Mode
. Set first test report time in field *83.
Maximum Test report interval is 0024 for Commercial Fire and Commercial
Burglary installations.
*28
Power-Up in Previous State
0 = disable
1 = enable
If enabled, the system, upon power-up, reverts to its status prior to a complete
power loss.
If disabled, the system always powers up in a disarmed state.
NOTES:
Neither authority level 0 nor 5 can be used to disarm the system if the control
powers up armed.
When Power Up in Previous State is enabled, if the panel powers up armed, it
may take up to 3 minutes before an alarm is recognized and initiated.
Must be 1 for UL applications.
*29
Quick Arm (partition-specific)
0 = disable
1 = enable
If enabled, allows arming of the burglary system in AWAY, STAY, INSTANT,
or MAXIMUM mode by using the [#] key instead of the user code.
NOTES:
When armed, the system reports closing as User 0 if Open/Close reporting for
User #2 (typically a Master level user) was enabled for a given partition.
If Quick Arm is used, the Installer Code and Authority Level 5 codes cannot
disarm the system.
Main Dialer TouchTone or Rotary
Dial
0 = rotary
1 = touchtone
Select the dialing method for the main dialer.
If you select TouchTone, make sure the subscriber has requested and is paying for TouchTone service. Note that
whether or not TouchTone dialing for call placement is permitted, communication by the use of DTMF signaling
(ADEMCO High Speed) will still take place. See field 1*33 for TouchTone w/Rotary backup.
*30
*31
PABX Access Code
Enter 00-09; B-F (11-15)
This field is used to enter up to four 2-digit numbers representing the prefix
needed to obtain an outside telco line. If not required, enter nothing and
proceed to next field.
*32
Primary Subscriber’s Account
Number (partition-specific)
Enter 00-09; B-F (11-15)
Enter a 3- or 4-digit (depending on report format) primary subscriber account
number. Each number requires a 2-digit entry so as to allow entry of
hexadecimal digits (B-F). If a 3-digit account number is to be used, enter data
only in the first three locations, and enter * in the fourth location.