Section 5 – Data Field Descriptions
5-11
FIELD TITLE and DATA ENTRIES EXPLANATION
1*52
Send Cancel If Alarm + Off
(partition-specific)
0 = disable
1 = enable
If enabled, Cancel reports are sent when the system is disarmed after an
alarm, regardless of how much time has gone by.
If disabled, Cancel reports are sent within Bell Timeout period only.
NOTES:
This option must be enabled so Cancel reports are always sent.
This field must be enabled for SIA installations.
1*53
Disable Download Callback
0 = callback required
1 = no callback required
Select whether a callback from the control panel is required for downloading.
Must be set to 0” for Commercial Fire and Burglary installations.
1*55
European Date Format
0 = disable (mm/dd/yy)
1 = enable (dd/mm/yy)
Select the date format for display in the event log.
1*56
AC 60Hz or 50Hz
0 = 60Hz
1 = 50Hz
Select the frequency for the AC.
Must be set to 0 for U.S. and Canadian installations.
1*57
Enable 5800 RF Button Global
Arm
0 = disable
1 = enable
If enabled, the system arms/disarms in accordance with the buttons users
global arming settings.
Must be 0 for Commercial Fire and Commercial Burglary installations.
1*58
Enable 5800 RF Button Force
Arm
0 = disable
1 = enable
If enabled, allows the RF button user to force a bypass of all faulted zones
when arming the system.
NOTE: When attempting to arm the system, the keypad beeps once after the
button is pressed if any faulted zones are present. The user should then
press the button again within 4 seconds to force-bypass those zones and arm
the system.
1*60
Zone 5 Audio Alarm Verification
0 = disable
1 = enable
If enabled, zone 5 is used for 2-way audio (AAV).
Must be set to 0” for UL commercial fire and burglary installations.
NOTE: Zone 5 cannot be used as protection zone.
1*69
Printer Type
Not Used.
1*70
Event Log Types
0 = disable
1 = enable
This field has five entries as follows: Alarm, Check, Bypass, Open/Close, and
System. If enabled, the system logs those events into the event log.
1*71
12/24 Hour Type Stamp Format
0 = 12-hour
1 = 24-hour
Select the type of time stamping for the event log.
1*72
Event Log Printer On-Line Mode
0 = disable
1 = enable
If enabled, the system prints the events as they occur.
If disabled, the system prints the log only upon request.
1*73
Printer Baud Rate
0 = 1200
1 = 300
Select the baud rate for the serial printer.
NOTE: Must be 1 if using the alphanumeric pager interface.
1*74
Relay Timeout XXX Minutes
Enter 000-127 times 2 minutes (000-254).
This is used for #80 Menu Mode Time-Driven event relay command numbers
04/09 and
Output Programming
in the
#93 Menu Mode Programming
output
command 56.
1*75
Relay Timeout YYY Seconds
Enter 000-127 seconds.
This is used for #80 Menu Mode Time-Driven event relay command numbers
05/10 and
Output Programming
in the
#93 Menu Mode Programming
command 57.