VISTA-128FBP/VISTA-250FBP Installation and Setup Guide
5-14
FIELD TITLE and DATA ENTRIES EXPLANATION
3*00
Check or TRBL Display
0 = CHECK
1 = TRBL
Select whether the system should display CHECK or TRBL when a trouble
condition occurs.
3*01
Event Display Lock
0 = disable
1 = enable
If enabled, the system locks the display on the first fire alarm. Press
to
display the next fire alarm in the system. If disabled, the system scrolls all
alarms automatically.
When 3*01 is Enabled, the following priorities go into effect:
The First event to occur is locked on the display; subsequent events will be
displayed in priority order:
Priority 1: Life Safety: ZT 06, 07, 09, 16, 17, and Duress override all other s
below
Priority 2: Property Safety: ZT 01, 02, 03, 04, 05, 10 override all other s below
Priority 3: Supervisory: ZT 14, 18, 19 and Fire Trouble override all other s
below
Priority 4: System: AC Loss, Low Bat, Line Cut, etc. do not override any other
events
NOTE: Must be set to 1 for Commercial Fire installations.
3*12
Zone Type 18 Delay Use
0 = disable
1 = enable
If enabled, use the delay time programmed in field 3
16.
3*13
Fire Supervisory Response to
Open/Short (Applies to Zone
Type 18)
0 = disable
1 = enable
If 0 is selected, the system will respond with a trouble on open, and a
supervisory on short.
If 1 is selected, the system will respond with a supervisory on open, and a
supervisory on short.
Must be set to 0 for Commercial Fire and Commercial Burglary installations.
3*14
Waterflow Alarm Silence Option
0 = silenced by User Code + OFF
1 = silenced when zone restores
Select how the Waterflow zone type will be silenced.
NOTES:
This feature may be set to 1 only by permission of the local authority.
For an output of a 4204CF to be silenced when 3*14=1, all Type 17
(Waterflow) zones activating the output must be put into a Zone List, and that
Zone List must be the STP condition of the 4204CF fire output. In addition to
the STP ZL, you also need an STP ZT of 22 in order to silence via code + off
in the event the zone does not restore.
Since a Type 17 zone is processed as a FIRE alarm, it will activate outputs
programmed for STT ZT 17, 16, 09, and 39. The only way to have individual
output activations (e.g. ZT17 versus ZT09) is to use zone lists.
NOTE: Must be set to 0 for Commercial Fire installations.
3*16
Zone Types 17 & 18 Delay
Enter 01-15 times 2 seconds
Enter 00 for no delay
Select the delay time for zone types 17 and 18. The zone must be faulted for
entire delay time before an alarm or supervisory condition occurs. This may
prevent alarms due to minor fluctuations in waterflow.
Maximum combined delay of3*16 and 3*18 cannot exceed 90 seconds for UL
installations.
NOTE: Must be set to 00 for Commercial Fire installations.
3*17
Zone 6 Alternate Function Enable
0 = disable
1 = enable
If enabled, zone 6 may be used as a tamper zone (bell and cabinet tampers).
If used, the zone will annunciate in accordance with response type, rather
than a ground fault when a ground fault is detected.
3*18
Extended Delay for Zone Types
17 & 18
0 = no extended delay
1 = multiply delay by 4
This option allows the delay programmed in field 3
16 for Waterflow and
Supervisory zones to be extended by 4 times.
NOTE: Must be set to 0 for Commercial Fire installations.