ADEMCO VISTA 10 Setup Guide Page 9

  • Download
  • Add to my manuals
  • Print
  • Page
    / 72
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 8
Wiring to Keypads
1. Connect keypads to the keypad terminals as shown on the Summary of Connections diagram.
Determine wire size using the Wire Run Chart below.
2. Set keypad addresses. Refer to the address setting instructions included with the keypads and set
each keypad device address according to the chart at right.
3. Program the keypad addresses and sound options in data fields *190-*196.
IMPORTANT: Each keypad must be assigned a unique address, starting at address 16.
Keypads programmed with the same address will give unpredictable results.
Supplementary Power (optional)
1. Connect as shown. Be sure to connect the negative (–) terminal on the power supply unit to terminal 4
(AUX –) on the control.
NOTES
Typical Fixed-Word Display: 6150
Typical Alpha Display: 6160
Voice Keypads: 6150V, 6160V
The system supports up to 8 keypads
(see program fields *190-*196).
For single 4-wire runs, determine the current
drawn by all units, then refer to the Wiring
Run chart to determine the maximum length
that can be safely used for each wire size.
Use supplementary power if the control’s aux.
power load for all devices exceeds 600mA.
Suggested power supply: AD12612
Keypad Addresses
Keypad Address Keypad Address
no. 1 16** no. 5 20
no. 2 17 no. 6 21
no. 3 18 no. 7 22
no. 4 19 no. 8 23
** The first keypad is address 16, which is always
enabled and set with all sounds on.
+
+
456 7
SUPPLEMENTARY
POWER SUPPLY
CONTROL TERMINAL STRIP
AUX.
AUX. DATA
IN
DATA
OUT
IMPORTANT:
MAKE THESE
CONNECTIONS
DIRECTLY TO
SCREW
TERMINALS AS
SHOWN.
TO KEYPAD RED WIRE
TO KEYPAD BLK WIRE
TO KEYPAD YEL WIRE
TO KEYPAD GRN WIRE
TO KEYPAD BLK WIRE
TO KEYPAD RED WIRE
TO KEYPAD GRN WIRE
TO KEYPAD YEL WIRE
supp_pwr_supply-V0
Figure 4. Using a Supplementary Power Supply
U
L
Use a UL Listed, battery-backed supply for UL installations. The battery supplies power to these keypads in
case of AC power loss.
The battery-backed power supply should have enough power to supply the keypads with the UL required
minimum standby power time.
Keypads powered from supplies that do not have a backup battery will not function if AC power is lost.
Make sure to power at least one keypad from the control’s auxiliary power output.
Wire Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)
Wire
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Size 50 mA or less 100 mA 300 mA 500 mA 600 mA
#22 900 ft (274m) 450 ft (137m) 150 ft (46m) 90 ft (27m) 75 ft (23m)
#20 1400 ft (427m) 700 ft (213m) 240 ft (73m) 140 ft (43m) 120 ft (37m)
#18 1500 ft (457m) 1100 ft (335m) 350 ft (107m) 220 ft (67m) 170 ft (52m)
#16 1500 ft (457m) 1500 ft (457m) 550 ft (168m) 350 ft (107m) 270 ft (82m)
* Includes Keypads, RF Receivers, Zone Expander/Relay Units, 4285/4286 Phone Module, and LRR.
Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on
the current draw of that device alone
.
The length of all wire runs combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet
if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.
Mounting and Wiring the Control
2-3
Page view 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 71 72

Comments to this Manuals

No comments