Type 06
24-hour Silent Alarm
Type 07
24-hour Audible Alarm
Type 08
24-hour
Auxiliary Alarm
Type 09
Supervised Fire
(With Verification on
Zone 1)
Type 10
Interior w/Delay
Type 23
No Alarm Response
Type 24
Silent Alarm
This zone type sends a report to the Central Station but provides no keypad
display or sounding. This zone type is usually assigned to a zone containing
an Emergency button.
This zone type sends a report to the Central Station, and provides an alarm -
sound at the keypad, and an audible external alarm. This zone type is usually
assigned to a zone that has an Emergency button.
This zone type sends a report to Central Station and provides an alarm sound
at the keypad. (No bell output is provided). This zone type is usually
assigned to a zone containing a button for use in personal emergencies, or to a
zone containing monitoring devices such as water or temperature sensors, etc.
This zone type provides a fire alarm on short circuit and a trouble condition
on open circuit. The bell output will pulse when this zone type is alarmed.
This zone type is always active and cannot be bypassed. This zone type can
be assigned to a control panel basic wired zone, any zone in a wired
zone expansion module, or wireless zones. When used with zone 1 on
the panel, 2-wire smoke detectors can be used. For an explanation of the
“verification” function, refer to the Operation paragraph in Section 5 under
Wiring 2-Wire Smoke Detectors To Zone 1.
Note: Only hardwired zone 1 can be programmed as a fire zone in UL
installations. However, any wireless zone can be used as a fire
zone.
This zone type gives entry delay #1 (using the programmed entry time), if
tripped when the panel is armed in the Away mode. Entry delay begins
whenever sensors in this zone are violated, regardless of whether or not an
entrylexit delay zone was tripped fwst. iVo entry delay is provided if tripped
when the panel is armed in the Maximum mode. Exit delay is present for any
arming mode. This zone type is bypassed when the panel is armed in
the Stay or Instant modes.
This zone type can be used on a zone when an output relay action is desired, w
but with no accompanying alarm (e.g., lobby door access).
This zone type provides an instant alarm, with NO audible indication at any
keypad or external sounder, if the zone is faulted when the system is armed
in the AWAY, STAY, INSTANT, or MAXIMUM modes. This zone type is
usually assigned to all sensors or contacts on exterior doors and windows
where audible notification is NOT desired. A report is sent to the Central
Station.