Press *48 REPORT FORMAT, PRIMARYJSECONDARY
Primary
Secondary
Determines which format is to be used to report to the central
station.
O= 3+1; 4+1 ADEMCO Lo Speed Standard (this is the default)
1 = 3+1; 4+1 Radionics Standard
2 = 4+2 ADEMCO Lo Speed Standard
3 = 4+2 Radionics Standard
6 = 4+2 ADEMCO Express
7 = ADEMCO Contact ID Reporting
8 = 3+1; 4+1 ADEMCO Lo Speed Expanded
9 = 3+1; 4+1 Radionics Expanded
(Enter *as the 4th digit of* 43 through* 46, if 3+1 dialer report
ing is to be used.)
Note: The maximum number of alarm and alarm restore reports
during one armed period is determined by field * 93.
Press *49 SPLIT/DUAL REPORTING
Enter Oto disable (Backup report only). This is the default.
Press *50
Press *51
Press *52
Press *53
TO PRIMARY TO SECONDARY
1=
Alarms,Restore, Cancel
Others
2=
All except Open/Close, Test
Open/Close, Test
3=
Alarms, Restore, Cancel
All
4=
All except Open/Close, Test
All
5= All
All
15-SECOND DIALER DELAY, BURGLARY
Enter Ofor no, or 1 for yes. Default is O(no delay).
Enter “O”for UL installations.
I
PERIODIC TEST REPORT
•1
Selectthe desired test report interval.
O= none; 1 =24 hours; 2 = weekly; 3 =30 days. Default is O
(none). Test Report Code entered in field* 64 is sent.
Reports with Partition 1 Subscriber No.
TEST REPORT OFFSET
This is the time to first report after exiting from programming or
downloading.
O= 24-houq 1 = 6 hours; 2 = 12 hours; 3 = 18 hours. Default is 2.
SESCOA/RADIONICS SELECT n
O= Radionics (o-9, B-F reporting)
1 = SESCOA (O-9 only reporting)
Select Ofor all other formats. Default is O.