ADEMCO Vista-20HW Troubleshooting Guide Page 66

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 65
TO PROGRAM
SYSTEM STATUS
AND RESTORE
REPORT CODES
(*59-*76,&*89)
The following is a set of guidelines to be used for programming report codes,
The actual digits that you enter depend upon the particular installation, and
should be in agreement with you and the central station office receiving the
signals. Use these guidelines to program this entire section.
With a 3+1 or 4+1 Standard Format: Enter a code in the first box
1-9, A,
B, C, D, E, or F. Enter “#+10” for A (this reports a “O” on some receivers),
“#+11” for B, “#+12” for C, “#+13” for D, “#+14” for E, “#+15” for F.
An entry of “O” in the first box will disable a report.
An entry of “O” in the second box will result in automatic advance to thf
next field when programming.
With an Expanded or 4+2 Formati Enter codes in both boxes (let and 2nd
digits) for 1-9, or A-F, as described above.
An entry of “O’ in the first box will disable a report.
An entry of “O”in the second box will eliminate the expanded message for
that report.
With Ademco Contact ID Reporting Enter a digit in the first box to
enable the zone to report. Use a difTerent digit for each zone until you have
used up available digits.
If the number of zones exceeds the number of
available digits, begin with digit 1 again. This is an “enabling” code only and
is not the actual code sent to the central station office. Entries in the second
boxes will be ignored. For system status (non-alarm) codes, enter a “1” in the
first box for all the system conditions you want to send to the central station.
An entry of “O”in the first box will disable the report.
Press *59 EXIT ERROR REPORT CODE
L-1
Press *6O
Press *61
Press *62
Press *63
Press *64
If “O” is entered in this field, no special message will be sent,
only the regular alarm and alarm restore code for the zone. If a
non-zero code is entered, this message will be sent if an alarm
occurs within 2 minutes after the end of the Exit time.
Refer to Section 17. DATA FIELD DESCRIPTIONS for a %
detailed description of this option.
Field %59 ent~ note:
The
2nd digit is automatically sent as
the 2nd digit of the zone alarm report code programmed in * 56,
if expanded or 4+2 reporting is selected.
TROUBLE REPORT CODE
m
I
This will be sent if a zone goes into trouble.
BYPASS REPORT CODE
M
This will be sent when a zone is manually bypassed.
AC LOSS REPORT CODE
n
I
Reports with Partition 1 Subscriber No. Timing of this report is
random with up to a 4-hour delay. If AC restores before the
report goes out, there is no AC restore report.
LOW BAT REPORT CODE
m
This will be sent when a low battery condition exists in the
system’s standby battery. Reports with Partition 1 Subscriber
No.
TEST REPORT CODE
n
I
This is sent periodically to test that the communicator and phone
lines are operational (frequency of report is selected in field
*51). Reports with Partition 1 Subscriber No.
-66-